background image

EMERALD PLANET HEAD OFFICE - SYDNEY

 Unit 2 / 29 Mitchell Road, Brookvale NSW 2100 Australia 

P

 02 9466 6000

PRACTICE FIRE SAFETY  

If the alarm sounds, and the test button has not been pressed, 
it is warning of a potentially dangerous situation. To prepare for 
such occurrences, develop family escape plans, discuss them 
with all household members, and practice them regularly.
1:  Familiarise everyone with the sound of a smoke alarm and 

explain what the sound means.

2: Determine possible exits from each room and an escape 

route to the outside from each exit.

3: Educate all household members to touch the door and use 

an alternate exit when the door is hot, instruct them not to 
open the door if the door is hot.

4: Teach household members to crawl along the floor to stay 

below dangerous smoke, fumes and gases.

5: Determine a safe meeting place for all members outside the 

building.

WHAT TO DO IN CASE OF FIRE

1: Do not panic, stay calm.
2: Leave the building as quickly as possible. Touch doors to 

feel if they are hot before opening them. Use an alternate 
exit if necessary. Crawl along the floor, and do stop to 
collect anything.

3: Meet at a pre-arranged meeting place outside the building.
4: Call the fire department from outside the building.
5: Do not go back inside a burning building. Wait for the fire 

department to arrive.

NOTE: 

THESE GUIDELINES WILL ASSIST YOU IN THE EVENT 

OF A FIRE, ALWAYS FOLLOW THE INSTRUCTIONS OF 
FIREFIGHTING PROFESSIONALS.

INSTALLATION POSITIONING ADVICE

When mounting an alarm on the ceiling, locate it a minimum 
of 30 cm from the side wall (see Diagram 6).
•  Put smoke alarms at both ends of a bedroom hallway or 

large room if larger than 10m long.

•  Install smoke alarms on slopped, peaked or cathedral 

ceilings between 500 and 1500mm from the highest point 
of the ceiling. Smoke alarms in rooms with ceiling slopes 
greater than 1m in 8 m horizontally should be located on 
the high side of the room (See Diagram 7)

DIAGRAM 7

PEAK CEILING PLACEMENT

Smoke alarm should be located between 
500mm and 1500mm from the highest point.

SLOPED CEILING PLACEMENT

DIAGRAM 5

MULTIPLE FLOOR PLAN

DIAGRAM 6

CEILING PLACEMENT

Отзывы: