“Set-Point Cl” (Proportional) mode - Pulse
This mode is valid for any proportional / pulse output available.
Proportional mode set the CONTROLLER to operate using a calculated percentage between two set values that
enable or disable the Cl pump. To use this mode tap on “Proportional First Point”. Tap on it.
PROPORTIONAL mode between 1.00Cl (0 p/m) and 0.50Cl(180 p/m). p/m is : pulses per minute
In this mode the Cl pump will be “ON” for values lower than 0.50mg/l with set pulses/minute capacity (e.g.: 180) and it’ll
be “OFF” for values greater than 1mg/l. For values of 0.75mg/l pump will be “ON” with 90 p/m capacity. The calculation
is based on 180 pulse / minute.
Tap on main function to enable / disable
Tap on value to change them according to preferences
Tap on Out to choose between any output available
1.00
0
0.50 180