V. OPERATING INSTRUCTION :

1.

Check the PT & Auxiliary fuses.

2.

Connect 110V / 230V A.C. Aux. Supply to pins 1 & 2 of the Rear Panel Terminal
Block.

3.

Connect PT Supply to pins 3 & 4 of the Rear Panel Terminal Block.

4.

Turn on the instrument by putting Power Switch to 'ON' position.

5.

Leave the unit on for 15 minutes before making any settings.

6.

Check the Test / Normal Switch is in the Normal mode.

7.

Make the following settings by changing selector switch.

NOMINAL VALUE

110V

LOWER VOLTS Setting

112V

RAISE VOLTS Setting

108V

TIME-DELAY Setting

30 Sec.

%R & %X Setting

‘0’ %

(in case of relay with LDC)

8.

Keep the selector switch to PT I/P position.

9.

Increase the PT voltage to read PT = 110V

10.

Note that under this condition all the lamps viz. L, R, LR, RR & UV/OV are off.

11. LOWER VOLTS OPERATION CHECK :

Increase the PT Supply above 112V (atleast 112.5V), but ensure that it is below
OV limit (132V). 'L' lamp should immediately turn on.

The 'LR' control pulse will come only after 30 secs. from the instant of turning on
of 'L' lamp. The control pulse will remain 'ON' for 2 secs, after which the Time
Delay of 30 secs. will restart & the control pulse will come again for 2 secs. & the
cycle is repeated. Check the LR contacts on pins 9-10 of the Rear Panel
Terminal Block.

12. RAISE VOLTS OPERATION CHECK :

Decrease the PT Supply below 108V (atleast 107.5V), but ensure that it is above
UV limit (88V). 'R' lamp should immediately turn on.

The 'RR' control pulse will come only after 30 secs. from the instant of turning on
of 'R' lamp. The control pulse will remain 'ON' for 2 secs, after which the Time
Delay of 30 secs. will restart & the control pulse will come again for 2 secs. & the
cycle is repeated. Check the RR contacts on pins 11-12 of the Rear Panel
Terminal Block.

5

Содержание EE301-T

Страница 1: ...Type EE301 T is designed for maximum operational simplicity It regulates the secondary voltage of power transformers with on load tapchangers The bandwidth control allows the dead band to be set in t...

Страница 2: ...ing at 132V Restoration at 127V Control Relays One pair of normally open potential free contacts of rating 5A at 240V AC or 24V DC resistive load for each Lower Raise Control Fail Undervoltage Overvol...

Страница 3: ...ergised 8 CF Lamp ON when Control Fail Relay is energised i e when the PT voltage remains outside the bandwidth for more than 15 minutes 9 TEST Lamp ON when AVR is in TEST mode B CONTROLS 1 Power ON T...

Страница 4: ...age gets connected to the instrument This switch must be kept in Normal mode when the instrument is in use 7 Test Voltage Control Simulates PT I P in Test mode and can be varied from 0V to 150V AC 8 T...

Страница 5: ...OLTS OPERATION CHECK Increase the PT Supply above 112V atleast 112 5V but ensure that it is below OV limit 132V L lamp should immediately turn on The LR control pulse will come only after 30 secs from...

Страница 6: ...east 132 5V UV OV lamp will turn on immediatelly Under this condition L lamp will also be on but the Lower control is inhibited Note that between Blocking Release Restoration a hysteresis of 5V has be...

Страница 7: ...rom 1 to maximum tap and check whether TPI reads correctly Keep the TPI Test Normal switch in Test mode check whether display reads 88 FUSE REPLACEMENT 1 After switching power on the display indicatio...

Страница 8: ...appropriate relay The NO contacts are brought out on the Rear Panel Terminal Block In case of UV OV condition the relays are blocked and no control pulses are available The IC8 is used to convert the...

Страница 9: ...ntrol to 108V Set selector switch to L set position and vary L set control to read 110 5V to 115 5V on display Set L set control to 112V Ifany of the settings are not obtainable it means Display PCB i...

Страница 10: ...n IC4 on Main PCB is faulty In above description it is assumed that display LEDs are OK Step 11 To check relay vary PT I P to get L R conditions in Normal mode confirm that Lower relay and Raise relay...

Страница 11: ...TP3 5V 0 25V On Display PCB Bet TP4 on Display PCB TP7 on Main PCB For PT I P 110VA C 3 3VAC 0 2 Bet TP1 on Display PCB TP7 on Main PCB For PT input 110V A C 7 5VDC 0 2 Varies with PT input DC O P Bet...

Страница 12: ...Replace after varying P T input beyond dead Display PCB band settings Or L or R indication remains permanently ON LR or RR not coming after varying Digital circuitary on Main PCB faulty PT I P voltag...

Страница 13: ...ty is selected by polarity switches The net compensation is then summed with the stepped down PT voltage II SPECIFICATION Resistive Reactive 0 20 of the regulating value continuously adjustable Compen...

Страница 14: ...e VX raises the voltage VX Lowers the Voltage The PT I P to the AVR is internally stepped down to 3 3V corresponding to 110V The vector sum of resistive reactive drops i e LDC 0 P is added vectorially...

Страница 15: ...se of its small effect on AVR VERY IMPORTANT 1 Switch off CT current or short CT before disconnecting AVR 2 When LDC is not to be used then both X and R dials should be kept at 0 This position will gi...

Страница 16: ...proportional to Taps 1 to 17 which can be used for SCADA TESTING PROCEDURE Check TPI for taps 1 to 17 measure O P current varies from 4 to 20mA 1mA tap i e tap1 4mA tap2 5mA so on till tap17 20mA In...

Страница 17: ...S 1 Block Diagram 05 ED 09 2 Front Panel View 05 MD 19 3 Rear Panel View with Cutout Dimensions AVR connections 05 MD 20 RECOMMENDED SPARES 1 Main PCB 2 Display PCB 3 TPI PCB 4 Mains Transformer 5 Sen...

Страница 18: ......

Страница 19: ...06 DRG No 05 MD 19 ISS 2 4 3 2 1 ISS DATE APPR BY DRN BY J J P MATERIAL ASSEMBLY PRODUCT AVR 301 T DATE 9 4 03 SCALE N T S EMCO ELECTRONICS DOC No DC00 405 ISS 1 ON VAC UV OV R RR L LR CF NSET RSET LS...

Страница 20: ......

Страница 21: ...case exceeds the original purchase price of the equipment For warranty service or repair the equipment must be returned to EMCO ELECTRONICS securely packed on Freight paid basis and accompanied by a...

Страница 22: ...s when Display rdg R SET 3 RR LED pulses after TD 4 L LED glows when Display rdg L SET 5 LR LED pulses after TD 6 UV glows for UV condition 7 OV glows for OV condition 8 CF glows for CF condition 9 AL...

Страница 23: ...t Thane 401208 Tel 0250 2481783 1804 Fax 0250 2481087 Email mumbai emcoelectronics org Office 302 Vasan Udyog Bhavan Sanapati Bapapat marg OPP Phoenix mill BIG BAZAAR Lower Parel W Mumbai 400 013 Tel...

Страница 24: ...ION 1 III SPECIFICATIONS 2 IV FAMILIARIZATIONWITH INDICATIONS CONTROLS 3 V OPERATIONINSTRUCTIONS 5 VI FUNCTIONAL DESCRIPTION OFVARIOUS MODULES 8 VII FAULT FINDING PROCEDURE 9 VIII OPTION 13 I X LIST O...

Страница 25: ...ISO 9002 COMPANY Automatic Voltage Regulating Relay EE 301 T INSTRUCTION MANUAL...

Отзывы: