Embedded Systems LM5 Lite Скачать руководство пользователя страница 3

 

Embedded Systems SIA © 2021

 

www.logicmachine.net

 

LM5Lp2 

Data sheet / Issue date 26.11.2021 

Page 3 / 10

 

 

Types of product 

 
LogiMachine5 Lite Power 

 

LM5Lp2 

 
 

Standards and norms compliance 

 
EMC:   

 

 

 

EN61000-6-1  

 

 

 

 

 

EN61000-6-3 

PCT 

 

 

 

 

Certificate 

 

 

Technical data: 

 
Power supply:  

 

 

24V DC on terminal connectors or  

24V DC Power-over-Ethernet  

 

 

Power consummation: 

 

1.3W 

 
Interface: 

 

 

 

KNX/EIB TP1   

 

 

 

 

 

 

10BaseT/100BaseTX  1 

 

 

 

 

 

RS-485  

 

 

 

 

 

 

 

RS-485/RS-232 

 

 

 

 

 

 

(switchable in software 

  

full-duplex=RS232,  
half-duplex=RS485)   

 

 

 

 

 

 

USB2.0  

 

 

 

 

 

 

 

Connections:   

 

 

KNX bus: 

 

 

Bus Connection Terminal 
0.8mm2 

Power supply:  

Screw, 1.5mm2 

 

 

 

 

 

Serial:   

 

 

Screw, 1.5mm2 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 
Operating elements   

 

LED 

 

 

 

 CPU load 

 

 

 

 

 

 

 

 

 

1 - Activity 

 
 
Enclosure: 

 

 

 

Material: 

 

 

Polyamide 

 

 

 

 

 

Color:   

 

 

Gray 

 

 

 

 

 

Dimensions:   

 

54(W)x90(H)x61(L) mm 

 
Usage temperature:   

 

0C ... +45C 

Storage temperature:  

-15C ... +55C 

Weight: 

 

 

 

150g 

Warranty: 

 

 

 

2 years 

Relative Humidity:  

 

 

10...95 % without condensation  

Содержание LM5 Lite

Страница 1: ...egrated Ethernet USB KNX EIB Serial interfaces LM allows to use it as cross standard gateway logic engine visualization platform IP Router Scripting templates provides user friendly flexible configura...

Страница 2: ...DA visualization for PC and touch devices cross standard gateway integration with third party devices over USB RS485 serial port Ethernet AV IR HVAC Data logger with trends KNX IP Router Presence moni...

Страница 3: ...net Power consummation 1 3W Interface KNX EIB TP1 1 10BaseT 100BaseTX 1 RS 485 1 RS 485 RS 232 1 switchable in software full duplex RS232 half duplex RS485 USB2 0 1 Connections KNX bus Bus Connection...

Страница 4: ...nt that supports directly or indirectly human health or life or with application that can result danger of people animals or real value Mounting advice The devices are supplied in operational status T...

Страница 5: ...Embedded Systems SIA 2021 www logicmachine net LM5Lp2 Data sheet Issue date 26 11 2021 Page 5 10 Terminal connection schemes KNX connection...

Страница 6: ...ne is definitive second one is software switchable either it works as RS 485 or as RS 232 If it is set up as full duplex it will operate as RS 232 and respective TX RX GND screw terminals should be us...

Страница 7: ...et Issue date 26 11 2021 Page 7 10 RS 232 connection If second serial port is set as full duplex in LogicMachine configuration it will operate as RS 232 and respective TX RX GND screw terminals should...

Страница 8: ...nals Jumpers up or down passive PoE powering over 24V DC Jumpers down when using active PoE 48V jumpers have to be UP or the product will be damaged Please note that there are two PoE types of PoE swi...

Страница 9: ...Embedded Systems SIA 2021 www logicmachine net LM5Lp2 Data sheet Issue date 26 11 2021 Page 9 10 Passive PoE switch Passive PoE adapters...

Страница 10: ...hernet 4 Connect Ethernet LAN cable coming from the PC Default IP configuration Login name admin Password admin IP address 192 168 0 10 Network mask 255 255 255 0 Reset device You can either reboot th...

Отзывы: