Emailair WS 090C Скачать руководство пользователя страница 7

CONNECT THE INDOOR TO THE OUTDOOR UNIT

The indoor unit contains a small quantity of Helium

.

 Do not unscrew the

nuts from the unit until you are ready to connect the tubing

.

 The outdoor

unit is supplied with sufficient refrigerant charge for a 6 m tubing length

.

For additional charge, please refer to outdoor unit nameplate

.

To prevent crushing, bend tubes using a bending tool.

NOTE: 

 Use refrigeration type copper tubing only.

1

.

 Use tubing diameter that corresponds to the tubing diameter of the

indoor  and outdoor units . Note that the liquid and suction tubes have
different diameters. (See tube size, torque tightening table.)

2

.

Place flare nuts on tube ends before preparing them with a flaring tool

.

Use the flare nuts that are mounted on the supplied outdoor and indoor
units

.

3

Connect the four ends of the tubing to the indoor and outdoor units

.

4

Insulate each tube separately, and their unions, with at least 6 mm of

insulation. Wrap the refrigerant tubing, drain hose and electric cables
together with a vinyl tape (UV protected).

REFRIGERANT TUBING

Fig. 15

1. INDOOR UNIT
2. Liquid tube (small dia.)
3. Suction tube (large dia.)
4. Plugs
5

.

 Flare nuts

6. Tubing insulation
7. Suction tube
8. Liquid tube
9

.

 OUTDOOR UNIT

10

.

 Flare nuts

11. Suction valve (larger)
12. Liquid valve (small)

Caution!

When unscrewing
the valve caps, do
not stand in front of
them or the
spindles at any
time, as the system
is under pressure.

Fig 15

7

Tightening
torques of unions
and valve caps:

TUBE SIZE

TORQUE

Liquid line 3/8"
Suction line 1/2"
Suction line 5/8"
Suction line 3/4"

30-35 N.M.
50-54 N.M.
75-78 N.M.
80-100 N.M.

Fig

.

 16

1. Wrench
2. Torque wrench
3. Union

Fig

.

 18

1. Suction valve
2. Service port
3.Liquid valve

Fig

.

 17

To prevent refrigerant
leakage, coat the flared
surface with
refrigeration oil

Fig 16

Fig 17

Fig 18

EVACUATION OF THE REFRIGERATION TUBES AND THE INDOOR
UNIT

After connecting the unions of the indoor and outdoor units, purge the
air from the tubes and indoor unit as follows:

1. Connect the charging hoses with a push pin to the low and high sides
of the charging set and the service port of the suction and liquid valves

.

Be sure to connect the end of the charging hose with the push pin to the
service port

.

2. Connect the center hose of the charging set to a vacuum pump

.

3. Turn on the power switch of the vacuum pump and make sure that
the needle in the gauge moves from 0 MPa (0 cm Hg) to -0.1 MPa
(-76 cm Hg). Let the pump run for fifteen minutes.

4. Close the valves of both the low and high sides of the charging set
and turn off the vacuum pump. Note that the needle in the gauge should
not move after approximately five minutes.

5. Disconnect the charging hose from the vacuum pump and from the
service ports of the suction and liquid valves

.

6. Tighten the service port caps of both suction and liquid valves.

7. Remove the valve caps from both valves, and open them using a
hexagonal Allen wrench.

8. Remount valve caps onto both of the valves

.

9. Check for gas leaks from the four unions and from the valve caps

.

Test with electronic leak detector or with a sponge immersed in soapy
water for bubbles.

Fig

.

 19

1. Charging set
2. Vacuum pump
3. OUTDOOR UNIT
4. Service valve

5

.

 Cap

6

.

 Suction valve

7

.

 Service valve

*

8

.

 Cap

9

.

 Liquid valve

10

.

 INDOOR UNIT

1

1. Suction flare connection

12. Liquid flare connection

In some models only

NOTE: For additional R-2

2

 charge of

various tubing lengths, refer to
outdoor unit nameplate

.

Fig 19

Содержание WS 090C

Страница 1: ...AIR CONDITIONER SPLIT WALL MOUNTED I N S T A L L A T I O N I N S T R U C T I O N S MODELS WS 090C WS 090H WS100H EMAILAIR ...

Страница 2: ...s 4 Unit location should not disturb neighbors with noise or exhaust air stream 5 Place the mounting pads under the unit legs 6 Install the outdoor unit as shown Refer to the technical and service manual for allowed distances 7 When the unit is installed on a wall install the drain connector hose as shown Fig 1 1 Bottom of outdoor unit 2 Drain connector Fig 2 Drain installation example ACCESSORIES...

Страница 3: ...Fig 3 1 To attach 2 To remove Fig 4 1 Mounting pads x4 Fig 3 Fig 4 ...

Страница 4: ...ONT INDOOR UNIT Removal of the right cover 1 Remove screw caps 2 from cover 1 2 Remove the three screws 3 3 Rotate the right cover to remove it Removal of the bottom cover 1 Remove screw caps 5 from the air outlet 2 Loosen the screws 6 of the air outlet 3 Pull the cover 4 down and then to the right to disengage it ELECTRICAL REQUIREMENTS 3 4 Fig 5 INSTALLATION OF THE MOUNTING RAIL 1 Figure 7 shows...

Страница 5: ...densed or rain water from penetrating back into the room 3 Trim the hole in the wall with a ø70 mm commercial plastic tube Fig 8 4 When installing the drain hose avoid traps and U bends The end of the drain hose should not be immersed in water Fig 10 1 Trap 2 U bend 3 End immersed in water 5 For a lefthand outlet lay the drain hose on the bottom of the indoor unit rear groove Fig 11 1 Electric cab...

Страница 6: ...ig 14a Fig 14b and Fig 14c Be sure to match the colored wires with the numbers shown on the indoor and outdoor unit terminal boards 4 Connect the yellow green ground wire to the ground terminal screw 5 Secure multiple wire power cable with the cable clamps 6 Fasten the twin wire cable to the power cable with cable ties Cooling only model For units above 10 KW THREE PHASE MODELS Fig 13 1 Terminals ...

Страница 7: ...Torque wrench 3 Union Fig 18 1 Suction valve 2 Service port 3 Liquid valve Fig 17 To prevent refrigerant leakage coat the flared surface with refrigeration oil Fig 16 Fig 17 Fig 18 EVACUATION OF THE REFRIGERATION TUBES AND THE INDOOR UNIT After connecting the unions of the indoor and outdoor units purge the air from the tubes and indoor unit as follows 1 Connect the charging hoses with a push pin ...

Страница 8: ...between hole sides and tubing with sealer 3 Attach wiring and tubing to the wall with clamps where necessary 4 Operate the air conditioner together with the customer and explain all functions 5 Explain filter removal cleaning and installation 6 Give the operating and installation manuals to the customer 8 ...

Страница 9: ...d 4108 Tel 07 3274 4177 Fax 07 3274 4152 TOWNSVILLE 1 5 Everett Street PO Box 149 Bohle Townsville Qld 4818 Tel 07 4774 6552 Fax 07 4774 4967 OSBORNE PARK 19 Howe Street Osborne Park WA 6017 Tel 08 9244 5699 Fax 08 9244 5437 ADELAIDE Suite 27 8 Greenhill Road Wayville SA 5034 Tel 08 8372 7866 Fax 08 8372 7816 ECP AUSTRALIA PTY LTD ACN 082 755 655 HEAD OFFICE VICTORIA NEW SOUTH WALES QUEENSLAND WES...

Отзывы: