CMeX50 Quick manual A4 English

Document id: 1090051

Version:  6.0  

Mechanics
Casing material

Polyamide

Protection class

IP20

Dimensions

90x65x107 mm

Weight

220 g

Mounting

Mounted on DIN rail (DIN 50022) 35 mm

Electrical connections
Power supply

Screw terminal 0.5-2.5 mm²

M-Bus master port

Screw terminal 0.5-2.5 mm²

M-Bus slave port

Pin terminal solid wire 0.6-0.8 Ø mm

Antenna

SMA-f

RS232

RJ45 8/8

USB-port

Mini USB type B

Environmental specifications

Operating temperature range

-25 °C to +55 °C

Storage temperature range

-40 °C to +85 °C

Pollution

Degree 2

Operating altitude

0-2000 m

Electrical characteristics
Nominal voltage

100-240 VAC (+/- 10%)

Frequency

50/60 Hz

Power consumption 

<6 W

Installation category

CAT 2

Integrated M-Bus Master
M-Bus standard

EN 13757

M-Bus baud rate

300 and 2400 bit/s

Maximum unit loads

32T/48 mA (can be extended with the 

CMex10-13S Series)

Maximum cable length

1000 m (100 nF/km, maximum 90 

Ω

)

Wireless M-Bus receiver
M-Bus standard

EN 13757-4

Wireless M-Bus modes

S1, T1, C1

Maximum numbers of wireless 
M-Bus devices

800

Radio frequency band

434 or 868 MHz

M-Bus slave interface
M-Bus baud rate

300 and 2400 bit/s

Power consumption

1T/1.5 mA

Approvals
EMC

EN 61000-6-2, EN 61000-6-3

Safety

EN 61010-1, CAT 2

Description

Part number

CMeX50 Wireless M-Bus Receiver (868 MHz)

1050062

CMeX50 Wireless M-Bus Receiver (434 MHz)

1050128

ORDERING INFORMATION

CONTACT INFORMATION

Elvaco AB Technical support:

Phone: +46 300 434300 
E-mail: [email protected] 
Online: www.elvaco.com

TECHNICAL SPECIFICATIONS

USB interface

 

The USB interface is used as a standard transparent M-Bus interface 
over USB. Use the included USB cable and connect to any standard 
USB master port. When using Microsoft Windows® operating systems, 
a virtual comport will automatically be generated when connecting the 
product to the computer. Additional USB drivers can be downloaded 
from the Elvaco web site: www.elvaco.com.

M-Bus 2-wire interface

 

The M-Bus 2-wire interface acts like any other M-Bus slave device on 
the 2-wire bus. The nominal current is 1T (1.5 mA). This interface can be 
directly used with any standard M-Bus master.

IR interface

 

The IR interface is used as a standard transparent M-Bus interface over 
IR. This port can be used together with M-Bus master products from 
Elvaco, i.e. CMe2100 and CMe3000. In this way it is possible to extend 
the product with TCP/IP and GPRS communication.

GETTING STARTED

1. 

Power up the module and press OK to enter password.

2. 

Press OK for default password 0000.

3. 

Press OK for 1. Installation. 

4. 

Move down with cursors to 2. Installation, clear and press OK. Press 

OK for confirmation.

5. 

The CMeX50 will listen for transmitting wireless M-Bus slaves and 
add them to meter list.

6. 

The installation will automatically stop after 60 minutes. It can also 
be stopped manually by pressing ESC and OK when the expected 
number of meters are found.

7. 

Press ESC and press OK for saving the meter list in CMeX50 
and quit installation. Press OK to enter main menu. All wireless 
meters are now available as wired meters on any of the interfaces 
described above.

TROUBLESHOOTING

When running installation, no wireless meters are found 
Please verify:
• 

CMeX50 antenna installation and position.

• 

Wireless M-Bus slave mode must be the same as configured 

CMeX50 wireless M-Bus mode.

CMeX50 does not respond to M-Bus master commands 
Please verify M-Bus status:
• 

Voltage over M-Bus slave device should be between 21-42 VDC.

• 

All M-Bus slave devices must have unique secondary or primary 
M-Bus addresses depending on addressing mode.

• 

Verify M-Bus slave baud rate used by M-Bus master. M-Bus master 
baud rate must be identical to the CMeX50 baud rate.

• 

Encrypted wireless M-Bus slaves without uploaded keys will send 
meter data in container mode. Add keys to corresponding meter 
using the LCD display or M-Bus commands. 

Change from T1/C1a/C1b mode to S1 mode or vice versa does not work:
• 

The CMeX50 needs to be switched off and on again to make the 
change take effect. 

SAFETY

The warranty does not cover damage to the product caused by usage in 
any other way than described in this manual. Elvaco AB can not be liable 
for personal injury or property damage caused by usage in any other way 
than described in this manual.