M-Bus Gateway for Fixed Network

IntroductIon

CMe3000 is a DIN-mounted M-Bus Gateway for Fixed 

Network. It is compatible with ABB meters equipped with IR 

interface and all other meters supporting the M-Bus protocol.

For more information about the product or for information in 

other languages, visit the Elvaco AB website, http://www.

elvaco.com.

overvIew

1. 

Serial number

2. 

Push button

3. 

M-Bus connector

4. 

Ethernet RJ 45 

connector

5. 

IR interface

6. 

PWR LED (green)

7. 

ERR LED (red)

8. 

LINK LED (yellow)

9. 

ACT LED (yellow)

10.  Power supply L
11.  Power supply N

MountIng

CMe3000 is mounted on a DIN-rail. The metallic clip on the 

bottom is used to attach and deatach the device from the 

rail. For safety reasons, a DIN-rail enclosure must cover the 

terminals.

Power suPPly

Screw terminal (10) and (11) are used to supply the device 

with power. The main supply voltage should be in the range of 

100-240 VAC with a frequency of 50/60 Hz. The power needs 

to be connected via a clearly marked and easily accessable 

switch to make sure the device can be switched of during 

service work. The switch must comply with IEC 60947-1 and 

IEC 60947-3.

IMPortAnt

• 

The installation must be performed by a qualified 

electrician or another professional with the required 

knowledge.

• 

The power supply must be protected with a 10 A circuit 

breaker of characteristics C or slow blow fuse.

ethernet connectIon

Connect a TP cable to the Ethernet RJ45 connector (4). 

On successful connection, the yellow LINK LED (8) will be 

permanently on. 

All equipment connected to the Ethernet RJ 45 connector 

must have double or reinforced insulation from mains to 

prevent the risk of electric shocks.

M-Bus 2-wIre

M-Bus is a multi-drop 2-wire bus with no polarity. CMe3000 

can drive up to 8 M-Bus unit loads (1 lunit load=1.5 mA). The 

number can be extended by using an M-Bus Master from the 

Elvaco CMeX10-13S Series.

Use a telephone cable (e.g. EKKX 2x2x0.5 mm) or standard 

mains type (1.5 mm

2

) to connect meters to the M-Bus 

connector (3). Do not exceed the maximum cable length of 

1000 m.

All equipment connected to the M-Bus must have double or 

reinforced insulation from mains to prevent the risk of electric 

shocks.

FActory reset

There are two different ways to reset the CMe3000 to factory 

default settings.

• 

Reset the product and use dynamic IP settings. 

Press and hold the push button (2) during start-up. Keep 

it pressed for 5 seconds until the ACT LED (9) begins 

to flash faster. Release the push button to perform 

the factory reset. After a restart, the product will be 

assigned an IP address from an available DHCP server.

• 

Reset the product and use static IP settings. 

Press 

and hold the push button (2) during start-up. Keep it 

pressed for 10 seconds until the ACT LED (9) begins 

to flash faster for a second time. Release the button to 

perform the factory reset. After a restart, the product 

will use the following IP settings: 

 

IP address: 192.168.0.10 

 

Netmask: 255.255.255.0 

 

Gateway: 192.168.0.1 

CMe3000 can also be reset via the System page in its 

integrated web interface. Through this menu, product reboots 

and software updates may also be performed.

logIn

CMe3000 is configured via its integrated web interface. Type 

the IP address of the product in the address field of a web 

browser. Log in using the following credentials:

Username: admin

Password: admin

IP settIngs

CMe3000 supports both static and dynamic IP settings. To 

configure IP settings, navigate to the “Network” section of 

the web interface. 

Click on “Configuration” and select what settings to use. 

The product may need to reboot after IP settings have been 

configured.

English

Ir InterFAce

The IR interface can be used with an ABB electricity meter or 

a product from the Elvaco CMeX Series. Remove the IR shield 

(5) and mount the CMe3000 right next to the other device 

with no space between the two. Do not remove the shield 

unless planning to use the IR interface. 