CMi6140
User’s Manual English
CMi6140
User’s Manual English
page | 22 (38)
[2022-09]
V1.2
"T2":0,"U2":"kWh","T3":0,"U3":"kWh","P":0,"PU":"W","F":0,"FU":"l/h",
"FT":26.25,"TU":"C","RT":26.50,"RU":"C","EF":"0x00000100"}
Pulse: Message format ID 68
Field
Description
Date and
Time
(see Note 1)
6
INT32
Date and Time (Type F),
e.g. 046Dxxxxxxxx
M-Bus Format F for Date & Time
Meter ID
(see Note 1)
(see Note 2)
6
BCD8
According to M-Bus EN13757-3 identification
field
e.g. 0C78xxxxxxxx
Energy E1
6-7
INT32
Heat energy
Example: 0406xxxxxxxx, 040Fxxxxxxxx
Energy E3
6-7
INT32
Cooling energy
Example: 0483FF02xxxxxxxx = xxxxxxxx Wh
Energy E8
7
INT32
Energy (m3 * °C)
Example: 04FF07xxxxxxxx = xxxxxxxx m3 *
°C
Energy E9
7
INT32
Energy (m3 * °C)
Example: 04FF08xxxxxxxx = xxxxxxxx m3 *
°C
Volume
6
INT32
Example: 0413xxxxxxxx
Info codes
7
INT32
Error and warning flags
Example: 04FD17xxxx
Note that this field is always 32 bits, even
when using MultiCal 403 which only reports
16 bits.
Kamstrup MCxx3 Heat Meters Info Codes
Date and
Time
(see Note 1)
6
INT32
Date and Time (Type F),
e.g. 046Dxxxxxxxx
M-Bus Format F for Date & Time
Meter ID
(see Note 1)
(see Note 2)
6
BCD8
According to M-Bus EN13757-3 identification
field
e.g. 0C78xxxxxxxx
Energy E1
6-7
INT32
Heat energy
Example: 0406xxxxxxxx, 040Fxxxxxxxx
Table 11: Meter register, combined message
Pulse: Message format ID 69
Field
Description
Date and Time
(see Note 1)
6
INT32
Date and Time (Type F),
e.g. 046Dxxxxxxxx
M-Bus Format F for Date & Time
Meter ID
(see Note 1)
(see Note 2)
6
BCD8
According to M-Bus EN13757-3
identification field
e.g. 0C78xxxxxxxx
Energy
6-7
INT32
Example: 0406xxxxxxxx, 040Fxxxxxxxx
Volume
6
INT32
Example: 0413xxxxxxxx
Pulse In A
84 or
224
7
INT32
Reads the registers corresponding to
the In A connector on the module.