DC/AC Inverter
INV222 & INV211
User Manual
Page 16 (20)
©2014. ELTEK DEUTSCHLAND GmbH.
Eltek_UM_INV222_and_INV211_E_R2.0.doc
8.2 Specific technical data INV211
Type designation
INV211-48/115-60
INV211-60/115-60
INV211-110/115-60
INV211-220/115-60
Article code*
501-011-595.2.128
501-011-695. 2.128
501-011-795. 2.128
501-011-895.128
DC input:
Nominal input
voltage.
48 VDC
60 VDC
108 VDC
216 VDC
Input voltage range
(V
IMIN
-V
IMAX
)
40.8 to 67.5 VDC
52 to 76 VDC
91.8 to 145 VDC
183.6 to 270 VDC
Reflected input voltage
ripple, psophometric
(CCITT-A-filter)
≤
1.8 mV
≤
1.8 mV
---
---
Nominal input
current
20.8 ADC
16.7 ADC
9.2 ADC
4.6 ADC
Recommended external
input fuse:
25 A
20 A
16 A
10 A
AC output:
Nominal output voltage 115 VAC -5 %, factory adjustment range: 105 to 135
VAC
Threshold value of the
output voltage
Factory-set default: V
O
< = 95 VAC; V
O
> = 127 VAC
Output frequency
60 Hz ±0.05 %, adjustable to 50 Hz at factory. Synchronization range by external static transfer
switch unit: 58 to 62 Hz or 48 to 52 Hz
Nominal output power
900 W/1125 VA @ cos phi=0.8
8.3 General technical data INV222 & INV211
DC input:
Inrush current
≤
Nominal input current
Overall efficiency
≥90 %
Internal input fuse
There is no internal input fuse available (recommendation for external fuses see
section 8.1 & 8.2)
AC output:
Nominal output current
9.8 AAC @ power factor= 0.8; 7.8 AAC @ power factor= 1.0 (resistive)
Output power factor range
0.5 inductive … 1 … 0.5 capacitive
Overload capability
130 % for 10 sec
Total harmonic distortion
<2 % at linear load
Crest factor
≤
3
Dynamic behaviour
≤
3 % for load transients between 10 % … 100 % … 10 % of nominal output
current (transient time
≤
0.3 ms)
Short circuit protection
Continuous short circuit proof, short circuit current 3 x Inom for approx. 3 sec
(with delayed restart)
Internal output fuse
There is no internal output fuse
External output fuse
10 A gL or MCB characteristic B
Standard equipment:
Monitoring
DC-input voltage, (V
IMIN
, V
IMAX
) with automatic switch ON/OFF function, AC-output
voltage (warning at Vo<, switch off at Vo>), over temperature and overload with
automatic switch off function
LED signalling
OPERATION (green), Vo OK (green), ALARM (red)
Electronic protection
Input under voltage, input over voltage, over temperature, overload and short
circuit protection
External synchronization
External synchronization by static transfer switch.