46
User’s
Guide
THEIA S String Inverters
357100.013
, Issue
2.0
, 2010 Aug
Isolation monitoring
The menu
Insulation monitoring
enables to check the insulation between solar generator
terminal and protective conductor.
Key
Function
Navigate within menu
ESC
Back to Main Menu
OK
Accept selected mode
Note:
Insulation monitoring is deactivated in the factory.
When the OK key is pressed, the inverter accepts the changed parameters.
Four operating modes are possible depending on the type of installation:
—
INSULATED
No connection installed between solar generator terminal and protective conductor
—
MINUS GROUNDED
Negative terminal of the solar generator is connected to the protective conductor
—
PLUS GROUNDED
Positive terminal of the solar generator is connected to the protective conductor
—
DEACTIVATED
Activate insulation monitoring
If the insulation monitoring is activated, the inverter constantly performs the insulation
monitoring.
If the insulation resistance is too low:
—
The inverter is separated from the mains until the error is resolved
—
The inverter shows an error message