Static Transfer Switch
STS207
User Manual
Page 22 (28
)
ELTEK VALERE DEUTSCHLAND ©2009
UM_STS207_WEB_E_R1.4
List of the possible alarm messages:
Alarm messages
Meaning/possible reason
Corrective action
Source Mains f.
Mains voltage or frequency not Ok
Check mains voltage
Source INV fail
INV voltage or frequency not Ok
Check INV voltage
Synchr. error
Mains and INV voltage are not
synchronous
No mains voltage or
frequency of mains voltage is not stable.
Inverter fail.
INV failure
CAN communication with one ore more INVs
failed or INV failure detected via CAN
INV redundancy
INV failure
The last redundant INV is not Ok!
e.g. INV count=3, INV red. count=2
error
active when two inverters are not OK!
INV count crit.
INV failure
The first not redundant INV is not Ok!
e.g. INV count=3, INV red. count=2
error
active when three inverters are not OK!
STS overtemp
STS over temperature
Check the air flow
Check admissible ambient temperature
STS overload
STS output current to high
Reduce load current
INV overload
Actual output current exceeds the
combined INV power
#
Reduce load current or
increase INV power by additional inverter
INV red. overl.
Actual output current exceeds the com-
bined and
not redundant
INV power
##
Reduce load current or
increase INV power by additional inverter
DC-voltage low
Battery voltage low
Check DC voltage system (CAN-Off command is
send to the inverters)
DC-voltage high
Battery voltage high
Check DC voltage system (CAN-Off command is
send to the inverters)
fan error
Internal fan error
Check air flow, change fan
Uout error
Output voltage < 95% Vin (Mains/INV)
Check output voltage
Ubatt< warning
Battery voltage < warning level
Check DC voltage system
Ubatt> warning
Battery voltage > warning level
Check DC voltage system
#
Example:
Case 1): The STS is running on Mains with an actual load of 3.0kVA. There are two INVs in-
stalled in the system, each one with a nominal output power of 2.25kVA but one of the INVs has
switched off by over temperature.
>> Even though the STS is measuring the INV voltage and declares "Source INV" as OK, it will not switch
back to INV because the actual output current exceeds the power of one INV!
Case 2): The STS is running on "Source INV" while one INV turns off, the STS will activate the "INV over-
load" error but will switch to "Source mains" not till then "Source INV" is also broken-down!
##
Example: The INV rack is running with three INVs (each 2.25kVA) from which one is configured as
redundant. If the STS output power exceeds 4.5kVA the error “INV red. overl.” will occur. The system
output power is too high for the two not redundant INVs!