List of the possible alarm messages: 

Alarm messages 

Meaning/possible reason 

Corrective action 

Source Mains f. 

Mains voltage or frequency not Ok 

Check mains voltage 

Source INV fail 

INV voltage or frequency not Ok 

Check INV voltage 

Synchr. error 

Mains and INV voltage are not  
synchronous 

No mains voltage or 
frequency of mains voltage is not stable. 

Inverter fail. 

INV failure  

CAN communication with one ore more INVs 
failed or INV failure detected via CAN 

INV redundancy 

INV failure  

The last redundant INV is not Ok! 
e.g. INV count=3, INV red. count=2 

 error  

active when two inverters are not OK! 

INV count crit. 

INV failure 

The first not redundant INV is not Ok! 
e.g. INV count=3, INV red. count=2 

 error  

active when three inverters are not OK! 

STS overtemp 

STS over temperature 

Check the air flow 
Check admissible ambient temperature 

STS overload 

STS output current to high 

Reduce load current 

INV overload 

Actual output current exceeds the 
combined INV power

#

 

Reduce load current or 
increase INV power by additional inverter 

INV red. overl. 

Actual output current exceeds the com-
bined and 

not redundant

 INV power

##

 

Reduce load current or 
increase INV power by additional inverter 

DC-voltage low 

Battery voltage low 

Check DC voltage system (CAN-Off command is 
send to the inverters) 

DC-voltage high 

Battery voltage high 

Check DC voltage system (CAN-Off command is 
send to the inverters) 

fan error 

Internal fan error  

Check air flow, change fan 

Uout error 

Output voltage < 95% Vin (Mains/INV) 

Check output voltage 

Ubatt< warning 

Battery voltage < warning level 

Check DC voltage system 

Ubatt> warning 

Battery voltage > warning level 

Check DC voltage system 

#

Example:

 

Case 1): The STS is running on Mains with an actual load of 3.0kVA. There are two INVs in-

stalled in the system, each one with a nominal output power of 2.25kVA but one of the INVs has 
switched off by over temperature. 
>> Even though the STS is measuring the INV voltage and declares "Source INV" as OK, it will not switch 
back to INV because the actual output current exceeds the power of one INV!  
Case 2): The STS is running on "Source INV" while one INV turns off, the STS will activate the "INV over-
load" error but will switch to "Source mains" not till then "Source INV" is also broken-down! 
 

##

Example: The INV rack is running with three INVs (each 2.25kVA) from which one is configured as 

redundant. If the STS output power exceeds 4.5kVA the error “INV red. overl.” will occur. The system 
output power is too high for the two not redundant INVs! 

Содержание STS207

Страница 1: ...STATIC TRANSFER SWITCH STS207 USER MANUAL UM_STS207_WEB_E_R1 4...

Страница 2: ...he general safety rules in accordance with IEC 364 must be observed The module is manufactured in accordance with applicable DIN and VDE standards such as VDE 0106 part 100 and VDE 0100 part 410 The C...

Страница 3: ...Revision Description of change Writer Date 00 Preliminary first edition RTH 2007 10 25 01 First edition RTH 2008 05 07 02 Minor text modifications screenshot Net Connection updated section Trouble Sh...

Страница 4: ...f the rear side connector 11 3 4 2 Pin assignment of the front side CAN Bus connector RJ11 12 3 4 3 Pin assignment of the front side Ethernet connector RJ45 12 3 5 Cooling Air flow direction 13 3 6 Co...

Страница 5: ...3 Front view 10 Figure 4 Rear side connector 11 Figure 5 Front side CAN Bus connector 12 Figure 6 Front side Ethernet connector 12 Figure 7 Module air flow 13 Figure 8 Sample screenshot 14 Figure 9 L...

Страница 6: ...stall the module only in areas with limited access to unskilled personnel Before starting work the electrical module must be disconnected from mains Make sure that the module is earthed Do not touch c...

Страница 7: ...ly It is intended for the operation in combination with inverters of series INV215 222 Con sequently AC consumer loads can be driven nearly without interruption if one of the two power sources fails T...

Страница 8: ...the consumer load if source Inverter fails or is overloaded i e distortions by short circuit behaviour or overload 2 2 2 Mains priority At the operating mode mains priority AC mains works as priority...

Страница 9: ...INV222 60 and for one static transfer switch STS207 24V or STS207LV including a wired backplane Material code 502 222 315 LV AC Rack ACR INV222 6 75 HV assembly set 19 sub rack 2U for max three inver...

Страница 10: ...D indicators LC Display and front connectors see the following sections The STS207 is equipped with One LC Display 4 x 16 characters Seven LED indicators STANDBY INVERTER MAINS LOAD ON INVERTER LOAD O...

Страница 11: ...n 2b AC Input 1 Inverter Phase L1 5b STS Output Phase L1 8b AC Input 2 Mains Phase L1 11b Common Neutral Conductor 16a CAN_L Signal low 17a CAN_V DC Supply 8 15V 18a 19a Synchronization SYNC STAT 2 20...

Страница 12: ...3 CAN_H Signal high 4 CAN_L Signal low 5 CAN_V DC Supply Ground 6 CAN_V DC Supply Ground 1 6 Figure 5 Front side CAN Bus connector socket outlet RJ11 6 pole 3 4 3 Pin assignment of the front side Ethe...

Страница 13: ...aces 3 6 1 CAN Bus The STS207 is equipped with a serial data interface in accordance with the Controller Area Network CAN specification The CAN Bus connection is integrated in the rear side connector...

Страница 14: ...urthermore the STS207 is fitted with a front side Ethernet interface 10 100MB for remote control via HTTP WEB server SNMP SMTP und SNTP The STS can be directly configured via PC Furthermore extensive...

Страница 15: ...the unit until the module connector touched the backplane connector 4 Increase the force until the unit fits in completely Avoid using too much force If the unit does not fit in begin again at step 2...

Страница 16: ...ated see menu 2 Load on Inv green Load feeding by source Inverter Load on Mains green Load feeding by source Mains Sync green Inverters are synchronized to mains phase and frequency red Collective Fai...

Страница 17: ...er is registered it is possible to call the parameters input current output current and status of all connected inverters in succession by pressing ENT The inverter number is shown in the first line o...

Страница 18: ...l alarm messages All active Delay LED CF LED time delay of the collective failure signal 1 60 sec 30 Delay Relay CF Time delay of the collective failure relay output 1 60 sec 30 LCD contrast Contrast...

Страница 19: ...Structure of the customer menu The customer menu can be entered from the Basic display by pressing ENT for approx three seconds and then press ENT again For a list of all selectable individual alarm m...

Страница 20: ...ic Transfer Switch STS207 User Manual Page 20 28 ELTEK VALERE DEUTSCHLAND 2009 UM_STS207_WEB_E_R1 4 Figure 11 Continuation of the customer menu The final display shows the currently used Firmware vers...

Страница 21: ...etween this checks depends on ambient conditions of the installed module 7 Trouble shooting If a failure occurs in the system the LED Alarm bell symbol is illuminated according to the adjustments in t...

Страница 22: ...not redundant INV power Reduce load current or increase INV power by additional inverter DC voltage low Battery voltage low Check DC voltage system CAN Off command is send to the inverters DC voltage...

Страница 23: ...l switching capacity 7kVA Overload capability 1000 for 10 ms fuse tripping of 32A is guaranteed Output frequency acc to the input frequency Transfer time 4ms Other specifications Monitoring functions...

Страница 24: ...front panel only with black imprint constructive parts anodized metal Dimensions W H D 106 4 88 4 335 mm Minimum installation depth 400mm in combination with an assembly set 19 sub rack Weight approx...

Страница 25: ...Static Transfer Switch STS207 User Manual Page 25 28 ELTEK VALERE DEUTSCHLAND 2009 UM_STS207_WEB_E_R1 4 8 1 Dimensional drawings Figure 13 Module dimensions...

Страница 26: ...Static Transfer Switch STS207 User Manual Page 26 28 ELTEK VALERE DEUTSCHLAND 2009 UM_STS207_WEB_E_R1 4 9 Your notes...

Страница 27: ...Static Transfer Switch STS207 User Manual Page 27 28 ELTEK VALERE DEUTSCHLAND 2009 UM_STS207_WEB_E_R1 4 Your notes...

Страница 28: ...HLAND GmbH GB Industrial Schillerstra e 16 D 32052 Herford 49 0 5221 1708 210 FAX 49 0 5221 1708 222 Email Info industrial eltekvalere com Internet http www eltekvalere com 2009 ELTEK VALERE DEUTSCHLA...

Отзывы: