To be selected only in case an F7 filter is installed at the supply air side (Fig.7.a)
Press OK to enter.
Use 

 or 

 to choose “Not installed” or “Installed”.

Press OK to select.
The factory setting (DEFAULT) is “Installed”. 

It allows to adjust the various speeds.
Press OK to enter.
Use 

 or 

 to choose speed 1, speed 2, speed 3 or Holiday.

Press OK to select.

The setting ranges are:
speed 1: 10% ÷ 80% 
speed 2: 20% ÷ 90% 
speed 3: 60% ÷ 100% 
Holiday: 10% ÷ 40%
Use 

 or 

 to increase or decrease the speed percentage.

Press OK to select.
Press ESC to go back to the previous menu.

The factory settings (DEFAULT) are:
speed 1: 40%
speed 2: 70%
speed 3: 100%
Holiday: 20%

Installer menu

6 Heating Threshold
7 Dehumidification
8 Speed Setting
9 Airflow Balancing
10 F7 filter

Installer menu

6 Heating Threshold
7 Dehumidification
8 Speed Setting
9 Airflow Balancing
10 F7 filter

It allows to adjust the balancing of the two airflows.
Press OK to enter.
“Supply airflow” is highlighted.
Press OK to enter.
The setting range is: -20% ÷ +20% 
Use 

 or 

 to adjust supply airflow against extract airflow.

Press OK to select.
Press ESC to go back to the previous menu.

The factory settings (DEFAULT) is 0%

Installer menu

6 Heating Threshold
7 Dehumidification
8 Speed Setting
9 Airflow Balancing
10 F7 filter

Installer menu

11 Filter Alarm interval
12 Working Hours Counter
13 Save settings
14 Load settings
15 Restore Default Settings

It allows to set the Filter Alarm period: the system has a timer which activates the “Filter” warning on the 
LCD at regular intervals.
Press OK to enter. 
Use 

 or 

 to choose among 2-3-6 months or OFF.

Press OK to select. 

The factory setting (DEFAULT) is 3 months if F7 filter is “Installed” or 6 months if F7 filter is “Not installed”

Installer menu

11 Filter Alarm interval
12 Working Hours Counter
13 Save settings
14 Load settings
15 Restore Default Settings

The system keeps trace of the actual working hours of the unit. This value cannot be changed. Data is 
saved both on the motherboard and on the control panel CTRL-DSP, to be safe in case of fault. 
Press OK to enter.
Press OK or ESC to go back to the previous menu.

Содержание VIGO400A

Страница 1: ...duct information 2 3 1 General 2 3 2 Dimensions and Weight 3 3 3 Connections 3 3 4 Space required 3 3 5 Rating label 4 4 Transport and Storage 4 5 Installation 4 5 1 Unpacking 4 5 2 Where how to insta...

Страница 2: ...vice should not be used for applications other than those specified in this manual The device is not intended for use by persons including children with reduced physical sensory or mental capacities o...

Страница 3: ...Winter condensation drainage Summer condensation drainage A B D C F E A B C D LEFT Connections from and to outside are set on the left side of the unit front view DEFAULT RIGHT Connections from and to...

Страница 4: ...on on the CTRL DSP point 7 2 Installer menu 3 Machine Orientation Move the F7 filter from the left to the right side Replace the ducting connection label on the top of the casing and the water drainag...

Страница 5: ...ion it can be installed in loft spaces and outbuildings Mount the unit on flat surface wall The unit must always be installed vertically It s important that the unit is completely leveled before it is...

Страница 6: ...lied to fix the wall fixing bracket 5 c Hook the unit at its bracket and fix it by means of the safety screw 5 d Connect the supplied condensation elbow s to the drainage hole s in the opening at the...

Страница 7: ...ns SLAVE input 1 10V J2 jumper for SLAVE mode AC power supply Heat output max 250Vac 5A Dehumidifier output max 250Vac 5A Boost momentary switch BST IAQ input Air Quality i e SEN CO2 HY input i e SEN...

Страница 8: ...t settings of the 0 10V signal to the motors Airflow and consumption refer to one single motor Table 6 b indicates the efficiency of the heat exchanger and of the condensation produced in different cl...

Страница 9: ...250 500 1 K 2 K 4 K 8K Tot 3m Intake 73 61 67 69 59 56 50 43 75 47 Supply 72 61 63 65 56 50 41 31 74 43 Extract 73 60 63 65 57 51 42 31 74 44 Exhaust 73 61 66 67 58 55 49 41 75 46 Breakout 71 64 62 67...

Страница 10: ...eset the Filter Alarm ESC key to exit and go back to the previous menu OK key to enter the selected menu to go DOWN with the menu selection to go UP with the menu selection to power off the ventilatio...

Страница 11: ...at speed 1 Press ESC or wait for about 60 sec to go back to the operation screen Fig 7 c In case of activation of either HY or IAQ sensor inputs OR logic the unit speed increases by 15 and the sensor...

Страница 12: ...boost speed Press OK to select The factory setting DEFAULT is 15 Time options are 15 30 45 60 Time is flashing use increase the time and to decrease Press OK to select User menu 1 Mode Selection 2 Bo...

Страница 13: ...entation 4 Bypass settings 5 Heating 6 Heating Threshold 7 Dehumidification 8 Speed Setting 9 Airflow Balancing 10 F7 filter 11 Filter Alarm interval 12 Working Hours Counter 13 Save settings 14 Load...

Страница 14: ...is installed at intake air side Fig 7 a HEAT output Fig 5 g is activated and heating icon displays on LCD when T21 HEATING THRESHOLD Fig 7 a POST the heating element is installed at supply air side Fi...

Страница 15: ...OK to enter The setting range is 20 20 Use or to adjust supply airflow against extract airflow Press OK to select Press ESC to go back to the previous menu The factory settings DEFAULT is 0 Installer...

Страница 16: ...2 Working Hours Counter 13 Save settings 14 Load settings 15 Restore Default Settings Installer menu 11 Filter Alarm interval 12 Working Hours Counter 13 Save settings 14 Load settings 15 Restore Defa...

Страница 17: ...ced during very cold weather in order to prevent ice inside the unit which could damage the heat exchanger In this case the ANTI FROST icon is activated on the LCD R 7 6 Maintenance can be carried out...

Страница 18: ...heat exchanger is removable for cleaning and maintenance during service Condensation drainage Depending on the relative humidity in the extract air condensation may occur on the cold surfaces of the...

Страница 19: ...ternal environmental conditions and on frequency of filter cleaning fig 8 f j k Clean the fans every year with a vacuum cleaner This may differ per situation depending on internal and external environ...

Страница 20: ...ean fan impellers Cleaning required 2 Check that the fans are firmly in place within the unit Excessive air noise 1 Check setting of fan speed on the CTRL DSP controller supplied 2 Check grilles and d...

Страница 21: ...n2 Control typology Local demand control o1 Maximum internal leakage rate 0 6 o2 Maximum external leakage rate 0 4 p1 Internal mixing rate N A p2 External mixing rate N A q Visual filter warning Visu...

Страница 22: ...s and labour following this period the warranty covers replacement parts only based on maintenance having being carried out in accordance with our literature and terms and conditions of sale Proof of...

Страница 23: ...23 NOTES...

Страница 24: ...Elta Fans Limited Building Services 46 Third Avenue Pensnett Trading Estate Kingswinford West Midlands DY6 7US United Kingdom T 44 0 1384 275800 F 44 0 1384 275810 E bs eltafans co uk CFI00042 03 0416...

Отзывы: