Elster SR113 Скачать руководство пользователя страница 4

4

Figure 2

1

2

3

5

This is the maximum inlet the regulator should operate at to insure complete lockup 
at no-flow conditions.

Maximum Recommended Inlet Pressure

increase outlet pressure; counterclockwise to decrease 
outlet pressure.
Establish the outlet pressure within the range limits of 

g. 

the pressure spring used.
To test for the regulator's ability to fully shut off (lock-up), 

h. 

shut off all flow downstream of the regulator.  At lock-up, 
the outlet pressure will be somewhat higher than the set 
pressure.  However, if the pressure continues to rise after 
3 seconds, the regulator must be repaired.  Observe for 
30 seconds.
When the set pressure is properly adjusted, 

i. 

depressurize and remove gauge(s) and lines.
Replace seal plug (4).

j. 

Pressurize and check all connections for leaks.

k. 

(Numbers in parentheses refer to Figure 2.)

Remove all shipping plugs from the valve body.

1. 

Use good piping practice.  Be sure piping and regulator are 

2. 

free of dirt, pipe dope and other debris.  Apply pipe dope to 
male threads only.
Install regulator.  Make certain it is installed correctly with 

3. 

inlet pipe connected to the inlet regulator connection and 
flow is in the direction as indicated by arrow located on 
valve body (1).  Elster American Meter suggests the vent 
point downward to prevent entry of water and debris.  By 
removing the two valve body bolts (2), the diaphragm case 
(3) may be rotated in 90-degree increments in relation to the 
valve body (1).  Replace and tighten the two valve body bolts 
(2) to 100 ±25 in. lbs.  A regulator installed within a building 
should be located as near as practical to the point of service 
line entrance.
Make sure inlet pressure is always less than the maximum 

4. 

recommended inlet pressure for the orifice size (see Table 
3). Turn gas on slowly.  If an outlet valve is used, it should be 
opened first.  Do not subject the regulator to a sudden surge 
of inlet pressure.
Assure that there are no leaks and all connections are tight.

5. 

The SR100 Series regulator is preset at the factory.  Should 

6. 

you decide to adjust the set pressure, perform the following:

Turn gas off and depressurize the system.

a. 

Install outlet pressure gauge.

b. 

Turn gas on slowly.

c. 

Establish a low flow rate between 45 and 55 SCFH.

d. 

Remove seal plug (4) with a 1" wrench.

e. 

Turn pressure spring adjustment screw (5) clockwise to 

f. 

Inside Installation:  A vent line of sufficient 

diameter to carry gas vented by the regulator to 

a safe outside location away from any opening in 

the building is required.  For all sizes of regulators, 

a 3/4" or 1" threaded vent is provided for a vent 

line.  Verify vent piping does not interfere with the 

vent flapper movement.
Outside Installation:  Care must be taken to prevent 

vent opening from freezing closed, becoming 

blocked, or allowing water to enter from any 

cause.  Particular consideration should be given to 

sites where flooding, snow, or freezing rain may 

be experienced.  The vent or vent line port should 

point vertically downward, and overhead protection 

should be used where necessary.

Installation

!

WARNING

SR100 Series Service Regulators

04 Elster American Meter

Table 3

Orifice Size

Inlet Pressure (PSIG)       

1/8" x 3/16"

125

3/16"

125

1/4"

125

5/16"

100

Содержание SR113

Страница 1: ...Instruction Manual SR100 Series Service Regulators ...

Страница 2: ...atter which may have accumulated during shipment or handling To prevent regulator damage and possible personal injury pressures must not exceed Maximum inlet pressure normal service P1 Depending on orifice size up to 125 PSIG see Table 3 on page 4 Maximum outlet pressure normal service P2 Depending on spring selection up to 2 PSIG see Table 1 on page 3 Maximum inlet pressure for abnormal or emerge...

Страница 3: ...f Valve Guide Valve Plunger Plunger Valve Assembly Top Valve Body Plate Diaphragm Screen Vent Gasket Seal Plug Nut Valve Body 7 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Pressure Spring Table 1 Table 2 Orifice SR100 Series Service Regulators 03 Elster American Meter Outlet Pressure Color Code Part Number 6 to 8 W C Blue Yellow 70017P138 7 to 12 W C Blue Red 70017P139 13 to 16 W C...

Страница 4: ... 2 to 100 25 in lbs A regulator installed within a building should be located as near as practical to the point of service line entrance Make sure inlet pressure is always less than the maximum 4 recommended inlet pressure for the orifice size see Table 3 Turn gas on slowly If an outlet valve is used it should be opened first Do not subject the regulator to a sudden surge of inlet pressure Assure ...

Страница 5: ...6 parts Pay particular attention to the proper positioning of the seal ring 5 in the groove Install the diaphragm case 3 on the valve body 1 Make 7 sure the vent is positioned so that it cannot become plugged or allow water to enter Replace and tighten the two valve body bolts 2 to 100 25 in lbs Proceed to Steps 4 5 and 6 of the Installation instructions 8 Regulators are pressure control mechanism...

Страница 6: ...place the pressure adjusting screw and turn adjusting 5 screw to about mid position Proceed to Steps 4 5 and 6 of the Installation instructions 6 on page 4 to set delivery pressure Maintenance CAUTION Maintenance CAUTION Replacing the Orifice Numbers in parentheses refer to Figure 4 Shut off gas supply and depressurize the system 1 Remove the two valve body bolts 2 securing the diaphragm 2 case 3 ...

Страница 7: ...SR100 Series Service Regulators 07 Elster American Meter ...

Отзывы: