SM700 Series 

Cold Water Meters

Instructions for Storage, 

Handli

ng and Installation

D-0085-10

This document covers 
the SM700 series 

Introduction

The SM700 series of cold water meters 
are designed to conform to AWWA C700/
C713 specification. The meters are rated at 
150psi (10 bar). The meter designation is 
indicated on the display facia and the case.
Air or air/water mixtures will typically 
have no damaging effect on the internal 
components of the meter and air flow 
through the meter will not be registered.

Handling and Storage 

The meter should be handled with care and 
must not be dropped or subjected to impact. 
It is recommended the meter be stored 
under controlled conditions, preferably at a 
temperature between 15°F (–10°C) & 105°F 
(+40°C) and kept away from direct sunlight. 
The meter should remain boxed, with the 
two plastic thread protection caps in place, 
until the point of installation. Do not carry 
the water meter by the attached cable.

Fitting should be undertaken by 
a competent trained installer.  
These instructions should be 
read and understood before 
commencing the installation.

Installation instructions

1.   Remove the two plastic thread protection caps before 

installation.

2.   The meter must be installed with the arrow pointing 

in the direction of the water flow.

3.   Cut the pipework to the correct size (see Table 1 for 

lay length). This is important to prevent tensile loading 
across the meter when tightening.

4.  Ensure that the pipework is aligned correctly prior to     
       installation of the meter. Do not use the meter as a  
       lever to align the pipework in any manner.
5.  Ensure that the pipes are flushed and sealing faces    
      are free from debris and contamination.
6.   Fit the meter to the service pipework in accordance 

with standard installation practice.

7.    Ensure that rubber or fibre sealing washers are fitted 

between the pipe and water meter connections.  
Where washers are supplied with the meter, these 
must be used. 

Do not

 use P.T.F.E tape or sealing 

paste to provide a water tight seal.

8.    Locate the nuts on the pipework onto the meter 

threads and screw on finger tight.  Care should 
be taken to prevent cross threading or stripping of 
threads when making the connection.

9.   Tighten the nut a further quarter to half a turn 

using a wrench. Typical torque 11 ft-lbs min. 
to 14.75 ft-lbs max. (15Nm min. to 20Nm max.). 

Do not over tighten.

10.  If the meter is connected 

do not 

solder or make any 

solder joints within 8 inches of the meter. If soldering is 
undertaken, aim torch away from meter at all times.

11.   Ensure the pipework is securely fixed to avoid 

vibration or bending across the meter.

12.  The meter should be installed away from sources 

of heat and out of direct sunlight.

13.  The meter installation should be protected 

from freezing.

14.  The meter can be fitted to horizontal, vertical or 

inclined pipework.

15.   When water has been turned on check all joints 

for signs of leakage.

16.   It is recommended to thoroughly purge the entire 

water system, including all valves and pumps, of  
air prior to recording any reading as required by  
the utility.

17.   For connection to a remote reading system, see 

the manufacturer's instructions and refer to table 2 
of these instructions for wire color assignments 
when required.

Note: 

Do not install the communications cable along or 

within 6 inches of existing cable runs.

Reading the meter

The reading is displayed on the totalizer module of the 
meter under a protective lid.  The display digits before 
the decimal point, surrounded by a black or both a 
black and white border on the facia, represent whole 
US gallons (gal.), cubic feet (ft

3

) or cubic meters (m

3

and the digits after the decimal point, surrounded by 
a red border, represent fractions of a gallon, ft

3

 or m

3

.  

When water is flowing a flashing square icon appears 
to the lower right of the display, but when the flow has 
stopped this indicator will be extinguished.
To read the meter using a remote reading system, 
refer to the manufacturer's instructions.

Maintenance requirements

The SM700 series of cold water meters typically 
do not require routine maintenance. The water meter 
is powered by a 3.6 volt battery. Low battery power 
is indicated by the display digits flashing on and off, 
at which stage the meter should be replaced. This 
should be undertaken within three months. 
The SM700 series of cold water meter features 
a removable battery pack to allow for disposal 
separately to the rest of the meter.  For battery pack 
removal instructions, please refer to the separate 
instructions numbered 

D-1001-1

.  

Note: 

The batteries used in this meter are potentially 

hazardous if damaged. Battery disposal should be 
undertaken with consideration to any requirements 
by law for the disposal of Lithium-thionyl 
chloride batteries.

Health & Safety information

In installations where the pipework is part of an 
electrical earthing circuit the inlet and outlet pipes 
must be connected by a permanently bonded 
electrical earth grounding strap.

Note: 

The battery carries a warning as follows:- Fire, 

explosion and severe burn hazard. Do not crush, 
recharge, disassemble, heat above 212°F (100°C) or 
incinerate. 

Do not

 short-circuit.

Contact Information:

United States 
Elster AMCO Water, LLC
10 SW 49th Avenue, Building 100 
Ocala, FL 34474 
T +1 800 874 0890
F +1 352 368 1950
 [email protected]
www.elsteramcowater.com

Due to our policy of continual improvement 
we reserve the right to change the specification 
without prior notice. 

Certified to

NSF/ANSI 61

Note:

 Only products 

bearing the NSF Mark 
are certified.