Commissioning
Switch on the system.
Open the gas supply.
Press the control valve button and hold down.
4
Electrically ignite the pilot burner.
▷
▷
Once the pilot flame is burning, hold the control
valve button for at least 30 s until the thermo-
electric voltage has built up and keeps the control
valve open.
5
Release the control valve button.
▷
▷
The main gas line on the control valve is opened,
the main gas can ignite.
▷
▷
Observe process.
Checking the safety time
6
Close the gas supply.
▷
▷
Once the pilot flame has gone out, the control
valve must shut off the main gas supply after 30 s
(“click”).
▷
▷
If the main gas supply is still open after 30 s,
check and correct the alignment and the distance
between pilot burner and main burner.
▷
▷
If the error still occurs: remove the unit and return
it to the manufacturer for inspection.
Tightness test
WARNING
To ensure that there is no danger resulting from a
leak, check the gas connections on the burner for
leaks immediately after the burner has been put
into operation.
ZTA
1,5 ×
p
e max
1
ZT 40
1,5 × p
e max
1
ZTI
1,5 × p
e max
1
Setting the gas/air mixture
▷
▷
In cases where the pilot flame is too small or too
large, the gas/air mixture can be adjusted using
the air slide valve.
▷
▷
Burner diagrams – see www.docuthek.com, doc-
ument type “Operating characteristic diagrams”.
ZTA
1
ZT 40
2
3
1
4
5
Retighten the grub screw on the air slide valve.
ZTI 55
2
3
1
ZT 40, ZTI 55
•
Follow the reverse procedure when reassembling.
▷
▷
Replace the seal between burner housing and
protective tube.