5
Assembly Instructions
enCore FC1
Operating Instructions
Page 53 of 97
•
maximum cable length:
500 m
Hints on parameterization
Branch
<device> – Basic System – I/O boards –
Board <x>: MFE7
Set the following values:
•
channel
A1+ A1−
or
A2+ A2−
: type
Current input
•
parameter
Power supply
:
− in case of active barrier output: value
Off
− in case of passive barrier output: value
On
5.4.7 HART Measurement Transmitter (EEx i) via ExMFE5 Board
Hazardous Area
Safe Area
enCore device
ExMFE5 board
P+
P+
SH
HART pressure
transmitter, EEx i
HART temperature
transmitter, EEx i
HART
communicator
Fig. 5-12: Example – HART pressure and temperature transmitter (EEx i) via ExMFE5