BCU 580 · Edition 11.15
96
10 .11 Password
Parameter 77
The password is designed to protect the parameter settings.
To prevent unauthorized changes to parameter settings, a
password is stored in parameter 77 (0000 to 9999). Changes
to parameter settings can only be made once this number has
been entered. The password can be changed using BCSoft.
Note the effect of parameter settings on the safe functioning
of your system.
10 .12 Fieldbus communication
Parameter 80
Fieldbus communication can be activated using parameter 80
when bus module BCM 500 is connected.
A device name must be entered in the automation system for
the unique identification of the control unit (BCU/FCU) in the
Profinet IO system.
Parameter 80 = 0: Off. Parameterization access using BCSoft
via Ethernet is still possible.
Parameter 80 = 1: with address check. The device name on
delivery for the BCU 580 is “not-assigned-bcu-580-xxx”. The
expression “not-assigned-” must be deleted or may be re-
placed with an individual name. The sequence xxx must be
identical to the address set on the BCM 500 using the code
switches (xxx = address in the range 001 to FEF).
Parameter 80 = 2: no address check. The device name can
be selected as specified by the automation system.
Parameters