A3 ALPHA Meter/Node (ILC2)
June 2008
Product Guide
7
Display List Items
The A3 ALPHA meter display is divided into different regions as shown in Figure
3. See Chapter 3, “Operating Instructions,” in the A3 ALPHA Meter Technical
Manual (TM42-2190) for more detailed descriptions of the LCD and its display
regions.
Figure 3. A3 ALPHA meter LCD
The display list for all displayable items, including the items relating to the ILC2
option board, can be programmed using Metercat meter support software.
ILC2 Option Board Error Codes
Unlike standard A3 ALPHA meter error codes, ILC2 option board error codes
must be programmed as a displayable item in the A3 ALPHA meter display list
using Metercat support software; otherwise, the meter LCD will not display any
indication that a condition exists that affects the ILC2 option board's operation.
Error conditions and codes identify the ILC2 option board error conditions and
the associated display quantity value. The quantity identifier is the same for all
ILC2 option board error codes and can be programmed to be any numeric char-
acter (represented by
i
in Table 1).
Table 1. Error conditions and codes
Error codes may be displayed in combination (for example,
iii 100100
), indicat-
ing that more than one error condition has been detected.
No error.
This code is displayed when no error condition exists in the ILC2
option board. Since ILC2 option board error codes must be programmed as dis-
play items, this code is used when no error condition is present in the ILC2
option board.
ARh
CUM
KW
RATE
TOTAL
RESETS
CONT
MAX
ABCD
PREV
SEAS
TEST
ALT
EOI
Quantity identifer
Display quantity
Potential
indicators
End of interval
indicator
Real energy
indicators
Alternate energy
indicators
Power/energy
units identifier
Display identifers
Operating mode
indicators
Condition
Quantity identifier Display quantity value
No error
iii
000000
Table CRC error
iii
000100
Configuration error
iii
001000
Shared memory error
iii
010000
Power fail data save error
iii
100000
DRAFT