description
Enables the input from the motion sensor.
considerations Must be disabled if a motion sensor is not fitted.
range
00 (disabled) or 01 (enabled)
global default
01 (enabled)
10.37
set point (SPC or SPF)
The table below details the set point (
S PC
or
S PF
) parameter.
display
description
Defines the compressor cut-out temperature during the ready mode. The set point (
S P
) temperature is
the lowest measured temperature under normal operating conditions.
The set point is displayed as
S PC
(set point Celsius) or
S PF
(set point Fahrenheit) depending on whether
the ems controller is set to use Celsius or Fahrenheit.
considerations Must be above the freeze-up protection (
dtt
) temperature.
range
-9.9 to 9.9°C (14 to 50°F)
global default
3.0°C (37°F)
ems75sz: -3.0°C (27°F)
10.38
saving restart period (Sr)
The table below details the saving restart period (
S r
) parameter.
display
description
Defines the maximum time allocated to reach the set point (
S P
) temperature from the
saving mode
tem-
perature.
considerations
l
Set and verified by OEMs through the test protocol to ensure that product temperatures are within specification
when outlets open.
l
Must be set in multiples of 30 minutes.
range
0 to 240 minutes (in multiples of 30 minutes)
global default
120 minutes
10.39
saving set point (SSP)
The table below details the saving set point (
S S P
) parameter.
ems55advanced and ems55Radvanced / General Use
80 of 84