Provides the option to end a defrost cycle as follows:
l
on the defrost duration (
dd
) only
l
on defrost duration (
dd
) or defrost termination temperature
(
dtd
).
If the defrost termination method (
dtF
) is set to use the defrost duration (
dd
) or the defrost termination
temperature (
dtd
), the ems controller ends the defrost cycle on the first to occur.
considerations
Defrost method (
dF
) must be set to 0
Used only with sub zero and OFC firmware.
Not available on GDC firmware.
range
00 (time[
dd
]) or 01 (time[
dd
] or temperature[
dtd
])
global default
01 (time or temperature)
10.22
Maximum defrost on demand time (dtO)
The table below details the maximum defrost on demand time (
dtO
) parameter.
Display
Description
Maximum defrost on demand time is the maximum time of a temperature based
defrost cycle.
Considerations
Available only with the ems55 series using
OFC
(
Open Front Cooler
) firmware.
This parameter may not appear in all firmware versions.
Range
10 to 120 minutes
Global default
30 minutes
10.23
freeze-up protection (dtt)
The table below details the freeze-up protection (
dtt
) parameter.
display
description
Defines the temperature to stop further cooling to prevent freeze-up due to low temperature.
considerations Must be set below the set point (
S P
) temperature.
range
-15 to 10ºC (5 to 50ºF)
global default
0.0ºC (32ºF)
ems75sz: -6.0°C (21°F)
ems55advanced and ems55Radvanced / General Use