Power Supply System 

KNX PS640+IP 

with Bus Functions and Ethernet Interface

  

 

Item Number 70145 

 

 

 

 

         

 

 

 

 

 

Installation and Adjustment 

 

Elsner Elektronik GmbH

 Control and Automation Technology 

Sohlengrund 16 | 75395 Ostelsheim | Germany 

Tel.: +49 (0) 70 33 / 30 945 - 0 | Fax: +49 (0) 70 33 / 30 945 - 20 

[email protected] | www.elsner-elektronik.de 

Содержание KNX PS640+IP

Страница 1: ...ernet Interface Item Number 70145 Installation and Adjustment Elsner Elektronik GmbH Control and Automation Technology Sohlengrund 16 75395 Ostelsheim Germany Tel 49 0 70 33 30 945 0 Fax 49 0 70 33 30...

Страница 2: ...0 Data memory 10 Operating data 12 Language 12 Addressing the power supply unit programming mode 12 Setting of parameters in the ETS 14 Parameters of the IP interface 14 Communication settings in the...

Страница 3: ...pid LAN IP backbone The KNX PS640 IP therefore also takes on the function of a line coupler In parallel the KNX PS640 IP can be used as interface for accessing the bus via IP Like this the KNX system...

Страница 4: ...0 V AC 50 Hz Power consumption Full load approx 28 W Standby approx 2 7 W Outputs KNX bus voltage 29 V reduced Output current max 640 mA short circuit proof 24 V DC not reduced Output current max 150...

Страница 5: ...ine coupler The physical address assigned to the KNX PS640 IP determines whether the device operates as a line or backbone coupler If the physical address is in the form of x y 0 x y 1 15 the router o...

Страница 6: ...ducing bus load The filter table is automatically generated by the ETS Because of the speed difference between the Ethernet 10 Mbit s and KNX 9 6 kbit s a far greater number of telegrams can be transm...

Страница 7: ...re to follow the operating instructions voids any and all warranty and guarantee claims After unpacking the device check it immediately for possible mechanical damage If it has been damaged in transpo...

Страница 8: ...onnections 4 and 5 are suitable for solid conductors up to 1 5 mm or conductors with fine wires Scheme KNX communication of IP interface and power supply unit The device has got two KNX interfaces one...

Страница 9: ...f the IP interface and the KNX functions of the power supply unit Parametrise the IP interface Use the product file of PS640 IP power supply unit item number 70142 For description of parameters please...

Страница 10: ...vated The line is switched to neutral and shorted The basic setting displays Reset is active No Reset not activated The power supply system works in normal operation 30 seconds A reset of 30 seconds i...

Страница 11: ...nal overvoltage incidents is displayed With key you return to the previous menu level Short circuit The number of short circuit incidents at the bus is displayed With key you return to the previous me...

Страница 12: ...s and press the key The display automatically jumps to the previous menu in the desired language With key you get back by one menu level to the basic setting Addressing the power supply unit programmi...

Страница 13: ...press the key The programming mode is active just as long the text Prog Mode active is shown To switch off programming mode move the cursor with the keys and to Off and press the key With key you get...

Страница 14: ...disable enable If a KNX failure is detected it is reported on the IP Return of the bus voltage is also reported IP address assignment automatic DHCP manual Automatic DHCP The IP address is automatical...

Страница 15: ...n IP The multicast IP address 224 0 23 12 was reserved KNXnet IP at the IANA Internet Assigned Numbers Authority for this purpose If a different multicast IP address is required it must lie within the...

Страница 16: ...be used in the local LAN the entry of 0 0 0 0 can remain unchanged Example of assigning IP addresses A PC is to be used to access the KNX PS640 IP IP address of the PC 192 168 1 30 Subnet of the PC 25...

Страница 17: ...block route Block No group telegrams of these main groups are routed to IP Route An additional page appears on which the routing of main groups 16 to 31 can be disabled or enabled in pairs Note The gr...

Страница 18: ...if they are routed to IP Answer with NACK Every received physically addressed telegram from KNX is responded to with NACK not acknowledge This means that communication with physically addressed telegr...

Страница 19: ...physically addressed telegram should be routed to KNX Broadcast telegrams block route Block No received broadcast telegrams are routed to KNX Route All received broadcast telegrams are routed to KNX...

Страница 20: ...he remaining additional addresses can be assigned directly by the device in which cast the learn button should be pressed for at least one second The automatic address allocation is performed as Conne...

Страница 21: ...02 C R T 5 Overload 0 normal 1 overload Output 1 002 C R T 6 external overvoltage 0 normal 1 overvoltage Output 1 002 C R T 7 internal overvoltage 0 normal 1 overvoltage Output 1 002 C R T 8 Short cir...

Страница 22: ...017 C R W 24 Threshold value Switching output Output 1 002 C R T 25 Threshold value Switching output block Input 1 003 C R W 26 Software version readable 217 001 C R Parameters of the power supply un...

Страница 23: ...ly if sending in case of change 1 100 Reset of the linie What shall be used for the reset display and keyboard Yes object permanent reset 1 reset 0 no reset No Yes object time reset 1 30 seconds reset...

Страница 24: ...setting options are similar to object overload 1 bit malfunction collection Object 1 bit malfunction collection This object results in a disjunction of the 1 bit malfunction objects do not send send i...

Страница 25: ...settings for hysteresis etc are not taken into account for the status collection Bit 6 current threshold status exceeded is set if the threshold value has been exceeded for 1 minute The bit is immedi...

Страница 26: ...Threshold value is set by Communication object The value communicated last shall be maintained not after restoration of voltage after restoration of voltage and programming Do not use for first commis...

Страница 27: ...w 0 TV hyst above 1 Switching delay from 0 to 1 none 1 s 2 s 5 s 10 s 2 h Switching delay from 1 to 0 none 1 s 2 s 5 s 10 s 2 h Switching output sends send in case of change send in case of change to...

Страница 28: ...the value of the parameter Switching output sends see Switching output Value of parameter Switching output sends Setting options Behaviour of the switching output with release in case of change do not...