Parameter setting

Sensor KNX T-UP gl

 • Version: 05.09.2022 • Technical changes and errors excepted.

Threshold value setting via parameter:

Set the threshold values and hysteresis directly.

Threshold value setting via a communication object:

Define, how the threshold value is to be received from the bus. Basically, a new value
can be received, or simply a command to increase or decrease.

During initial commissioning, a threshold value must be defined, which will be valid
until the first communication with a new threshold value. For units which have already
been taken into service, the last communicated threshold value can be used. Basically,
a temperature range is given, in which the threshold value can be changed (object val-
ue limit).

A set threshold value will be retained until a new value or a change is transferred. The
current value is saved, so that it is retained in the event of a power supply failure and
will be available once the power supply is restored.

Set the 

hysteresis

 independent of the type of threshold value specification.

Switching output

Set the behaviour of the switching output when a threshold value is exceeded/under-
cut. The output switching delay can be set using objects or directly as a parameter.

Threshold value setting via

Parameter

 • Communication objects

Threshold value in 0.1°C

-300 … 800; 200

Threshold value setting via

Parameter • 

Communication objects

The value communicated last shall be 
maintained 

• never 
• after power supply restoration
• after power supply restoration and 
  programming

Start threshold value in 0.1°C
valid until first communication

-300 … 800; 200

Object value limit (min)

 

in 0.1°C

-300…800

Object value limit (max)

 

in 0.1°C

-300…800

Type of threshold value change

Absolute value • Increase/decrease

Increment 

(upon increase/decrease change)

0,1 °C • ... • 5°C, 1°C

Hysteresis in % of the threshold value

0 … 50; 20

When the following conditions apply, 
the output is
(TV = Threshold value)

• TV above  = 1 | TV - hyst. below  = 0 
• TV above  = 0 | TV - hyst. below  = 1 
• TV below = 1 |TV + hyst. above = 0 
• TV below = 0 |TV + hyst. above = 1

Delays can be set via objects
(in seconds)

No • Yes

Содержание 70631

Страница 1: ...KNXT UP gl Temperature Sensor Item numbers 70631 black 70632 pure white EN Installation and Adjustment...

Страница 2: ......

Страница 3: ...shold value 1 2 3 12 5 4 1 1 Threshold value 12 5 4 1 2 Switching output 13 5 4 1 3 Block 14 5 5 Temperature PI control 15 5 5 0 1 General control 15 5 5 1 General set point values 17 5 5 1 1 Set poin...

Страница 4: ...n this manual Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous situation which will lead to death or severe injuries if it is...

Страница 5: ...ter conclusion of all installation and operational start up tasks and only in the sur roundings designated for it Elsner Elektronik is not liable for any changes in norms and standards which may occur...

Страница 6: ...ured as 1 bit or 2 x 8 bits 2 actuating variable comparators for output of minimum maximum or average values Each with 5 inputs for values received via communication objects 3 Commissioning Configurat...

Страница 7: ...External measured value for tem perature Input RC 9 1 DPT_ Value_Temp 2 Bytes 4 Internal measured value for tem perature Output R CT 9 1 DPT_ Value_Temp 2 Bytes 5 Total measured value for tempera tur...

Страница 8: ...T 1 1 DPT_Switch 1 Bit 21 Temp thresholdV 2 Switching output block Input RC 1 2 DPT_Bool 1 Bit 22 Temp thresholdV 3 Absolute value Input Output RWCT 9 1 DPT_ Value_Temp 2 Bytes 23 Temp thresholdV 3 1...

Страница 9: ...1 Bit 42 Temp control Setpoint Standby cooling Input Output RWCT 9 1 DPT_ Value_Temp 2 Bytes 43 Temp control Setpoint Standby cool 1 0 Input RC 1 1 DPT_Switch 1 Bit 44 Temp control Setpoint Eco hea t...

Страница 10: ...N 0 OFF Output R CT 1 1 DPT_Switch 1 Bit 135 Actuating variable comparator 1 Input 1 Input RC 5 1 DPT_Scaling 1 Byte 136 Actuating variable comparator 1 Input 2 Input RC 5 1 DPT_Scaling 1 Byte 137 Act...

Страница 11: ...xxx 1 Byte 156 AND logic 2 Switching output block Input RC 1 2 DPT_Bool 1 Bit 157 AND logic 3 1 bit switching output Output R CT 1 1 DPT_Switch 1 Bit 158 AND logic 3 8 bit output A Output R CT 5 5 xx...

Страница 12: ...put RC 1 2 DPT_Bool 1 Bit 193 OR logic 4 1 bit switching output Output R CT 1 1 DPT_Switch 1 Bit 194 OR logic 4 8 bit output A Output R CT 5 5 xxx 1 Byte 195 OR logic 4 8 bit output B Output R CT 5 5...

Страница 13: ...transfer characteristics and select whether or not malfunction ob jects should be sent 210 Logic input 11 Input RC 1 2 DPT_Bool 1 Bit 211 Logic input 12 Input RC 1 2 DPT_Bool 1 Bit 212 Logic input 13...

Страница 14: ...alues The menus for setting the thresh old values are displayed 5 4 1 Threshold value 1 2 3 Threshold value Set in which cases threshold values received via object are to be retained The pa rameter is...

Страница 15: ...ce the power supply is restored Set the hysteresis independent of the type of threshold value specification Switching output Set the behaviour of the switching output when a threshold value is exceede...

Страница 16: ...ange to 0 and periodically Cycle only if sending periodically is selected 5 s 10 s 30 s 2 h Use switching output block No Yes Analysis of the blocking object At value 1 block At value 0 release At val...

Страница 17: ...temperatures for the individual modes Objects are used to determine which mode is to be selected A change of mode may be triggered manually or automatically e g by a timer window contact The mode may...

Страница 18: ...Heating and or cooling may be controlled in two lev els Mode after reset Comfort Standby Eco Building protection Behaviour of the blocking object with value 1 Block 0 release 0 block 1 release Blockin...

Страница 19: ...maintain the daily nominal value for a longer time e g when having guests The duration of this comfort extension period is set After the comfort extension period is terminated the system returns to e...

Страница 20: ...nt value is used as a basis If the comfort setpoint value is used as a basis the reduction increment of the value is set Eco setpoint Eco mode is usually used for night mode Starting heating cooling s...

Страница 21: ...t protection mode General control variables This setting appears for the control types Heating and Cooling only Here you can decide whether to use a common control variable for heating and cooling If...

Страница 22: ...t of the parameters for PI control Specify the deviation from the setpoint value at which the maximum control variable value is reached i e the point at which maximum heating power is activated The re...

Страница 23: ...et a value greater 0 OFF to receive a basic heating level e g for floor heating On release the control variable follows the rule again In case of a common control variable for heating and cooling 0 is...

Страница 24: ...rol in which either control parameters can be entered or predetermined applications can be selected In the 2nd level therefore only for 2 level cooling cooling is controlled via a PI or a 2 point cont...

Страница 25: ...able for heating and cooling 0 is always transmitted as a fixed value PI control with predetermined application This setting provides fixed parameters for a cooling ceiling Now specify what should be...

Страница 26: ...tput maximum minimum and median values 5 6 1 Control variable comparator 1 2 Determine what the control variable comparator should output and activate the input objects to be used Send behaviour and b...

Страница 27: ...o 8 bit objects Determine what the out put should send if logic 1 and 0 Send cycle is only sent if periodically is selected 5 s 10 s 30 s 5 min 2 h Analysis of the blocking object at value 1 block at...

Страница 28: ...Bit object two 8 bit objects Output value if logic 1 1 0 Output value if logic 0 1 0 Object type Value 0 255 Percent 0 100 Angle 0 360 Scene call up 0 127 Output value object A if logic 1 0 255 100 3...

Страница 29: ...ut 6 inverted Logic input 7 Logic input 7 inverted Logic input 8 Logic input 8 inverted Logic input 9 Logic input 9 inverted Logic input 10 Logic input 10 inverted Logic input 11 Logic input 11 invert...

Страница 30: ...perature controller active Standby temperature controller inactive Temperatur controller frost heat active Temperatur controller frost heat inactive Temp control status heating 1 Temp control status h...

Страница 31: ......

Страница 32: ...tronik under Tel 49 0 70 33 30 945 250 or service elsner elektronik de We need the following information to process your service request Type of appliance model name or item number Description of the...

Отзывы: