26

Parameter setting

Sensor KNX AQS/TH-B-UP

 • as of software 3.1 • Status: 24.09.2014 • Technical changes reserved. Errors reserved.

Switching output

Set the behaviour of the switching output when a threshold value is exceeded/under-
cut. The output switching delay can be set using objects or directly as a parameter.

Block

The switching output can be blocked using an object. Define specifications here for the
behaviour of the output when blocked.

The behaviour of the switching output on release is dependent on the value of the pa-
rameter "Switching output sends" (see "Switching output")

When the following conditions apply, the 
output is
(LV = Threshold value)

• LV above  = 1 |LV - hysteresis below  = 0 
• LV above  = 0 |LV - hysteresis below  = 1 
• LV below = 1 |LV + hysteresis above = 0 
• LV below = 0 |LV + hysteresis above = 1

Delays can be set via objects
(in seconds)

No • Yes

Switching delay from 0 to 1

(when delay is not set using objects)

None • 1 s • 2 s • 5 s • 10 s • … • 2 h

Switching delay from 1 to 0

(when delay is not set using objects)

None • 1 s • 2 s • 5 s • 10 s • … • 2 h

Switching output sends

• on change 
• on change to 1 
• on change to 0 
• on change and periodically 
• on change to 1 and periodically 
• on change to 0 and periodically

Send cycle 

(is only sent if "periodically" is selected)

5 s • 10 s • 30 s… • 2 h

Use switching output block

No • Yes

Analysis of the blocking object

• At value 1: block | At value 0: release 
• At value 0: block | At value 1: release

Blocking object value before 1st communi-
cation 

0 • 1

Behaviour of the switching output

With blocking

• Do not send message 
• send 0 
• send 1

On release
(with 2 seconds release delay)

[Dependent on the "Switching output 
sends" setting]

Switching output sends on change

• Do not send message 
• Send switching output status

Switching output sends on change to 1

• Do not send message 
• If switching output = 1 

 send 1

Switching output sends on change to 0

• Do not send message
• If switching output = 0 

 send 0

Содержание 40239

Страница 1: ...onik GmbH Control and AutomationTechnology Herdweg 7 D 75391 Gechingen Phone 49 0 70 56 93 97 0 info elsner elektronik de Germany Fax 49 0 70 56 93 97 20 www elsner elektronik de Item numbers 40239 wh...

Страница 2: ...4 Transfer protocol 14 4 1 List of all communications objects 14 5 Parameter setting 23 5 1 Behaviour on power failure restoration of power 23 5 2 General settings 23 5 3 Measured values Temperature h...

Страница 3: ...10 CO2 PI control 41 General control 42 Controller target value 42 Ventilation control 43 5 11 Variable comparator 44 5 11 1 Control variable comparator 1 2 44 5 12 Logic 45 AND logic 45 OR logic 45...

Страница 4: ...eshooting of the device must only be carried out by a competent electrician Safety advice Safety advice for working on electrical connections components etc DANGER indicates an immediately hazardous s...

Страница 5: ...4 Clarification of signs...

Страница 6: ...om the bus e g date time The housing is completed with a frame of the switching series installed in the building and thus merges with the interior Functions Measurement of CO2 concentration of the air...

Страница 7: ...ble for the switching programme used in the building 1 1 Technical specifications Housing Plastic material partly lacquered Colours White glossy similar to RAL 9016 Traffic White Aluminium matt Anthra...

Страница 8: ...of the bus voltage if the sensor has been in contact with fresh air 350 450 ppm at least once in this period After this the CO2 sensor will recalibrate every two weeks by defining the lowest measured...

Страница 9: ...follow the operating instructions voids any and all warranty and guarantee claims After unpacking the device check it immediately for possible mechanical damage If it has been damaged in transport in...

Страница 10: ...ing or cooling of the building structure on which the sensor is mounted e g due to sunlight heating or cold water pipes Connection lines and ducts which lead from warmer or colder areas to the sensor...

Страница 11: ...to the metal frame so that sensor and frame are fixed 2 5 Notes on mounting and commissioning Never expose the device to water e g rain or dust This can damage the electronics You must not exceed a r...

Страница 12: ...the ETS setting selected the mode display will only display show the current target value or the base target value setting with scale display The manually adjustable range can be set in the ETS The fo...

Страница 13: ...pressed for Priority 1 operating modes The individual operating modes can also be locked for manual selection in the ETS Comfort mode Comfort present target temperature will be used Standby mode Stand...

Страница 14: ...Ambient temperature in the current mode is increased The sep size is defined in the ETS 0 1 C to 5 C Change mode press left or right button longer than 2 secs Changes between the operating modes Comfo...

Страница 15: ...ut 1 001 C R T 3 Outside temperature reading Input 9 001 C W 4 Inside temperature reading Output 9 001 C R T 5 Overall temperature reading Output 9 001 C R T 6 Min max temperature value request Input...

Страница 16: ...C W 26 Temp threshold value 3 Switching output Output 1 001 C R T 27 Temp threshold value 3 Switching output block Input 1 002 C W 28 Reserve 29 TR_1_ Eco Standby HVAC 1 Input 1 003 C W 30 TR_1_ Comf...

Страница 17: ...N 0 OFF Output 1 002 C R T 54 TR_1_ Cooling status 1 1 ON 0 OFF Output 1 002 C R T 55 TR_1_ Cooling status 2 1 ON 0 OFF Output 1 002 C R T 56 TR_1_ Comfort Delay Status Input Output 1 002 C R W T 57 T...

Страница 18: ...et value Input Output 9 007 C R W T 80 Humidity controller Target value 1 0 Input 1 002 C W 81 Humidity controller Control variable dehumidification stage 1 Output 5 001 C R T 82 Humidity controller C...

Страница 19: ...2 threshold value 1 Switching delay from 0 to 1 Input 7 005 C W 107 CO2 threshold value 1 Switching delay from 1 to 0 Input 7 005 C W 108 CO2 threshold value 1 Switching out put Output 1 001 C R T 109...

Страница 20: ...troller Target value Input Output 9 008 C R W T 130 CO2 controller Target value 1 0 Input 1 002 C W 131 CO2 controller Control variable venti lation stage 1 Output 5 001 C R T 132 CO2 controller Contr...

Страница 21: ...AND logic 2 Block Input 1 002 C W 157 AND logic 3 1 bit switching output Output 1 002 C R T 158 AND logic 3 8 bit output A Output 5 010 C R T 159 AND logic 3 8 bit output B Output 5 010 C R T 160 AND...

Страница 22: ...C W 193 OR logic 4 1 bit switching output Output 1 002 C R T 194 OR logic 4 8 bit output A Output 5 010 C R T 195 OR logic 4 8 bit output B Output 5 010 C R T 196 OR logic 4 Block Input 1 002 C W 197...

Страница 23: ...8 bit object 3 for display Input 5 xxx C R W 235 16 bit object 1 for display Input 9 xxx C R W 236 16 bit object 2 for display Input 9 xxx C R W 237 Text message 1 for display Input 16 000 C R W 238...

Страница 24: ...cteristics and select whether or not malfunction ob jects should be sent 5 3 Measured values Temperature humidity CO2 The setting options for temperature humidity and CO2 readings are the same Use Off...

Страница 25: ...lues for air hu midity and four threshold values for carbon dioxide Table of CO2 values 1000 ppm corresponds to 0 1 CO2 content 5 4 1 Threshold value 1 2 3 4 Temperature humidity CO2 The settings opti...

Страница 26: ...M so that this is retained in the event of a power sup ply failure and will be available once the power supply is restored Threshold value setpoint using Parameter Communications object Temperature Th...

Страница 27: ...s Switching delay from 0 to 1 when delay is not set using objects None 1 s 2 s 5 s 10 s 2 h Switching delay from 1 to 0 when delay is not set using objects None 1 s 2 s 5 s 10 s 2 h Switching output s...

Страница 28: ...r priority The objects are coded as follows Alternatively you can use three objects with one object switching between eco and standby mode and the two others are used to activate comfort mode or frost...

Страница 29: ...Heating and or cooling may be controlled in two levels Mode after reset Comfort Standby Eco Building protection Behaviour of the blocking object at value 1 block 0 release 0 block 1 release Blocking...

Страница 30: ...the daily nominal value for a longer time e g when having guests The duration of this comfort extension period is set After the comfort exten sion period is terminated the system returns to eco mode...

Страница 31: ...is usually used for night mode If set point values are entered separately A starting set point value is defined as well as a temperature range in which the nom inal value may be modified Min object v...

Страница 32: ...the 2nd level has a common variable this is also where you determine the control mode of the 2nd level 5 5 2 Heating control level 1 2 If a heating control mode is configured one or two setting secti...

Страница 33: ...is reached You should set the time appropriate to the heating system at this point note manufac turer instructions Now determine what should be transmitted when the control is blocked Set a value grea...

Страница 34: ...d be transmitted when the control is blocked Set a value greater 0 OFF to receive a basic heating level e g for floor heating Upon release the control variable follows the rule again Application Warm...

Страница 35: ...activated The reset time shows how quickly the controls react to deviations from the set point value In case of a short reset time the controls react with a fast increase of the varia ble In case of...

Страница 36: ...be transmitted when the control is blocked Upon release the control variable follows the rule again In case of a common variable for heating and cooling 0 is always transmitted as a fixed value Contr...

Страница 37: ...s setting The status object shows the current status of the output variable 0 OFF 0 ON and can for example be used for visualisation Controller target value The target values can be set directly in th...

Страница 38: ...h the target value can be changed object value limit A set target value will be retained until a new value or a change is transferred The cur rent value is saved in EEPROM so that this is retained in...

Страница 39: ...r the humidification dehumidification system at this point note manufacturer instructions Now determine what should be sent when the control is blocked On release the control variable follows the rule...

Страница 40: ...am ming do not use during initial setup Offset in C only if the offset is not retained or retained after restoration of power 0 20 3 Step size for offset change using communi cation object 0 1 C 0 2 C...

Страница 41: ...ically is selected 5 s 10 s 30 s 2 h Use switching output block No Yes Analysis of the blocking object At value 1 block At value 0 release At value 0 block At value 1 release Blocking object value bef...

Страница 42: ...use the following settings to define control type target values and ventilation Send behaviour never periodically on change on change and periodically From change of is only sent if on change is sele...

Страница 43: ...ined via the bus using a communications object Target value setting using parameter Set the target value directly Setting a target value via communications object Enter how the target value will be re...

Страница 44: ...ariable value is reached i e the point at which maximum output is used The reset time shows how quickly the contro responds to deviations from the target value In case of a short reset time the contro...

Страница 45: ...it object 0 1 Value in if a value is sent for an 8 bit object 0 100 Use comparator 1 2 No Yes Output delivered Maximum value Minimum value Average value Use input 1 2 3 4 5 No Yes Output sends on chan...

Страница 46: ...prior to 1 communication for Logic input 1 16 0 1 Logic 1 2 3 4 5 6 7 8 not active active Logic 1 2 3 4 5 6 7 8 not active active 1 2 3 4 Input do not use all switching events which are available to...

Страница 47: ...Blocking object value before 1st communi cation 0 1 Behaviour of the switching output With blocking do not send message send value for logic 0 send value for logic 1 Value of the parameter Send behavi...

Страница 48: ...input 10 inverted Logic input 11 Logic input 11 inverted Logic input 12 Logic input 12 inverted Logic input 13 Logic input 13 inverted Logic input 14 Logic input 14 inverted Logic input 15 Logic input...

Страница 49: ...ication 1 inv Humidity control status dehumidification 2 Humidity control status dehumidification 2 inv Humidity control status humidification Humidity control status humidification inverted Switching...

Страница 50: ...tivated in order to be able to select external data Two line display Line 1 upper case Line 2 upper case Three line display Line 1 lower case Line 2 upper case Line 3 lower case You can switch from ei...

Страница 51: ...control No Yes Type of temperature target value display only for active thermostat display Current target value Basic setpoint Basic setpoint as bar chart Basic setpoint as bar chart with count Basic...

Страница 52: ...riables page 31 If certain modes should not be selected using pushbuttons these can be blocked for manual selection here By default Building protection mode cannot be selected No Use input objects No...

Страница 53: ...sed and when these are sent Changeover switching If the pushbutton is to be used for changeover switching select the function Change over switching and define which values are sent when the button is...

Страница 54: ...be sent using the pushbutton select the 8 bit encoder function and define the value to be sent Function Changeover switching Command when pressing the pushbutton Changeover switching Do not send mess...

Страница 55: ...between short and long is set individually Standard inverted When pushed shortly the drive moves up to the end position When pushed for longer the drive moves incrementally or stops The time differen...

Страница 56: ...ired The move can be stopped by briefly pushing Dead man s switch The drive moves as soon as the button is pushed and stops as soon as the button is released Point in time 0 Push of button start of ti...

Страница 57: ...and Operation EN WS1000 Color Control System for Buildings and for Conservatories Elsner Elektronik GmbH Control and AutomationTechnology Herdweg 7 D 75391 Gechingen Phone 49 0 70 56 93 97 0 info els...

Отзывы: