Temperature and humidity parameters
Smoke alarm Salva KNX
• Version: 09.09.2016 • Technical Changes and Errors excepted.
etc.). The building protection mode may be activated with delay, which allows you to
leave the building before the controls switch to frost/heat protection mode.
General control variables
This setting appears for the control types "Heating
and
Cooling" only. Here, you can
decide whether to use a common control variable for heating and cooling. If the 2nd
level has a common control variable, you also determine the control mode of the 2nd
level here.
When using the control variable for a 4/6 way valve, the following applies:
0%...100% heating = 66%...100% control variable
OFF = 50% control variable
0%...100% cooling = 33%...0% control variable
8.3.1. Heating control level 1/2
If a heating control mode is configured, one or two setting sections for the heating le-
vels are displayed.
In the 1st level, heating is controlled by a PI control, which allows to either enter control
parameters or select predetermined applications.
In the 2nd level (therefore only in case of 2-level heating), heating is controlled via a PI
or a 2-point-control.
Setpoint frost protection (in 0.1°C)
-300…800; 70
Activation delay
less than • 5 s • ... • 5 min • … • 2 h
Setpoint heat protection (in 0.1°C)
-300…800; 350
Activation delay
less than • 5 s • ... • 5 min • … • 2 h
For heating and cooling
• separate control variables are used
• common control variables are used for
Level 1
• common control variables are used for
Level 2
• common control variable are used for
Level 1+2
Use control variable for 4/6-way valve
(only for common control variables
in level 1)
No • Yes
Control type
(for level 2 only)
• 2-point-control
• PI control
Control variable of the 2nd Level is on
(only for level 2 with 2 point controlling)
• 1 bit object
• 8 bit object