15
Maintenance
Smoke alarm Salva KNX
• Version: 09.09.2016 • Technical Changes and Errors excepted.
4.1. Function test
BEWARE!
Danger of hearing damage!
During the function test (pressing on the light transmission bar),
a loud, shrill tone is sounded (at least 85 dB).
•
Keep a minimum distance of 50 cm between smoke alarm and ear.
1. Conducting a visual inspection:
Check:
•
Is the device found at the expected position?
•
Are the smoke entry openings clean? - Remove dust if necessary. The device
must not be painted over.
•
Is the device free from mechanical damage? - Replace the device if it is
damaged.
2. Conducting a function test:
If the function test is successful, a signal tone sounds. The smoke alarm works proper-
ly. If there is no signal tone, the device is not functioning. In this case, replace the bat-
tery and conduct the function test again. If there is still no signal tone, the device is de-
fect and must be replaced.
Smoke alarms must be replaced with new devices after a maximum
period of 10 years according to DIN 14604.
4.2. Replace the battery
The device is supplied with 9 V voltage from a battery. Lack of battery capacity is sig-
nalled optically and acoustically for 30 days and transmitted to the bus.
Fig. 10
Press the light transmission bar for at least 1
second.
Fig. 11
Separate the smoke alarm from the skirting
by turning it anti-clockwise.
Содержание Salva KNX basic