Wind Sensor P04i-W
2
Wind Sensor P04i-W
• Version: 25.06.2020 • Technical changes and errors excepted. • Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany • www.elsner-elektronik.de •
Technical Service: +49 (0) 7033 / 30945-250
Pole installation
The device is installed on the pole with the enclosed clamp.
2.1.4. Attaching and connecting the device
Connect the loose end of the connection cable to the P04i data collector. Use the
connection sockets and clips included for this purpose.
Use the
red and black wires
for +24 V DC and GND (polarity independent). Yellow
and white are not assigned.
The feed to the wind sensor may only be a maximum of 100 m long. The connection
is made with off-the-shelf UV-resistant telephone cable (A-2Y(L)2Y 2x2x0.6 or A-
2Y(L)2Y 2x2x0.8).
2.2. Notes on mounting and commissioning
Remove all existing protection labels after installation.
The correct wind value may only be supplied about 30 seconds after the supply vol-
tage has been connected.
WARNING!
Risk of injury caused by components moved automatically!
The automatic control can start system components and place people
in danger.
•
Always isolate the device from the mains for servicing and
cleaning.
The device must regularly be checked for dirt twice a year and cleaned if necessary.
In case of severe dirt, the sensor may not work properly anymore.
ATTENTION
The device can be damaged if water penetrates the housing.
•
Do not clean with high pressure cleaners or steam jets.
3.
Disposal
After use, the device must be disposed of or recycled in accordance with the legal
regulations. Do not dispose of it with the household waste!
Fig. 6 Bottom view
Insert the clamp in the mount through
the recess. Tighten the clamp on the
pole.
Make sure that the arrows are pointing
upward.
Pole
3
2
1
Fig. 7
1. Slide the device onto the mounting from above.
2. Tighten the screw of the mount to secure the device.
3. Screw the M8 connectors of the connection cable onto the connection
socket on the bottom side of the device.