19
Parameter setting
KNX K8 actuator
• Status: 18.11.13 • Technical Changes and Errors excepted.
variable. In case of a long reset time, the controls react somewhat more gently and
needs longer until the necessary variable for the set point deviation is reached.
You should set the time appropriate to the heating system at this point (note
manufacturer instructions).
Now determine what should be transmitted when the control is blocked. Set a value
greater 0 (=OFF) to receive a basic heating level, e.g. for floor heating.
Upon release, the control variable follows the rule again.
In case of a common variable for heating and cooling, 0 is always transmitted as a fixed
value.
PI control with predetermined application:
This setting provides fixed parameters for frequent applications.
Now determine what should be transmitted when the control is blocked. Set a value
greater 0 (=OFF) to receive a basic heating level, e.g. for floor heating.
Upon release, the control variable follows the rule again.
In case of a common variable for heating and cooling, 0 is always transmitted as a fixed
value.
Maximum control variable is reached
at set point/actual difference of (in °C)
0...5
Reset time (in min.)
1…255; 30
When blocked, the variable shall
• not be transmitted
• send a specific value
Value (in %)
only if a value is transmitted
0...100
Control type
•
PI control
Set control using
• Controller parameter
•
provided applications
Application
• Warm water heating
• Floor heating
• Convection unit
• Electric heating
Maximum control variable is reached
at set point/actual difference of (in °C)
Warm water heating: 5
Floor heating: 5
Convection unit: 4
Electric heating: 4
Reset time (in min.)
Warm water heating: 150
Floor heating: 240
Convection unit: 90
Electric heating: 100
When blocked, the variable shall
• not be transmitted
• send a specific value
Value (in %)
only if a value is transmitted
0...100