11
Setting the parameters
Room Temperature Controller KNX eTR 101-BA2
• Version: 20.04.2021 • Technical changes and errors excepted.
Behaviour on bus restoration of power and following programming or reset:
The device sends all outputs according to their send behaviour set in the parameters
with the delays established in the "General settings" parameter block.
7.2.
General settings
Set basic characteristics for the
data transfer.
Set the initial value for LED brightness. Determine if the
LED display should be con-
trolled via objects.
This activates input objects 5 and 6 for LED brightness. And set
whether the LEDs switch off automatically after pressing a push button.
7.3.
Temperature measured value
Determine is a
malfunction object
should be used. This activates output object 7 for
error messages.
Use
Offsets
to adjust the readings to be sent.
The unit can calculate a
mixed value
from its own reading and an external value. Set
the mixed value calculation if desired.
If an external portion is used, all of the following settings are related to the overall read-
ing. The display of
KNX eTR 101-BA2
also shows the total measured value.
Send delay in seconds after reset and bus
voltage recovery
5...7200
Maximum message rate
• 1 message per second
• ...
• 10 messages per second
• ...
• 50 messages per second
Initial LED brightness in % until first com-
munication
0...100; 10
Control LEDs with objects
No • Yes
Use automatic switching off of the LEDs
after using the push button
No • Yes
Switching off after
(if automatic switch off
is used)
1 ... 255; 2 Sec. after operation
Use malfunction object
No • Yes
Offset in 0.1°C
-50…50; 0
Use external reading
No •
Yes
Ext. Measured value portion of the total
reading
5% • 10% • ... • 50% • ... • 95% • 100%
All following settings refer to the total measured value