Setting of parameters
Indoor Sensor KNX AQS/TH
• Date of issue: 13.10.2011 • Subject to technical changes. Errors excepted.
4.10. Comfort field
Standard values comply with DIN 1946
Hysteresis of the temperature: 1°C
Hysteresis of the relative humidity: 2% RH
Hysteresis of the absolute humidity: 2 g/kg
4.11. CO2 measured value
If no external measured value is used:
Transmission behaviour
• not
• periodically
• on change
• on change and periodically
From change of
(only if sending „on change)
0,1 g • 0,2 g • 0,5 g • 1,0 g • 2,0 g • 5,0 g
Transmission cycle
(only if sending „periodically“)
5 s • 10 s • 30 s… • 2 h
Use comfort field
No • Yes
Transmission behaviour
• not
• periodically
• on change
• on change and periodically
Transmission cycle
(only if sending „periodically“)
5 s • 10 s • 30 s… • 2 h
Maximum temperature in °C
(Standard 26°C)
25 ... 40
Minimum temperature in °C
(Standard 20°C)
10 ... 21
Maximum relative humidity in %
(
Standard 65%)
52 ... 90
Minimum relative humidity in %
(Standard 30%)
10 ... 43
Maximum absolute humidity in 0,1g/kg
(Standard 115 g/kg)
50 ... 200
Offset in ppm
-100 … +100
Use external measured value
No • Yes
Use external measured value
No
Measured value
• not
• periodically
• on change
• on change and periodically