53
Parameter setting
Sensor KNX AQS/TH-B-UP
• as of software 3.1 • Version: 01.03.2017 • Technical changes and errors excepted.
16 bit encoder:
If a fixed 16-bit value should be sent using the pushbutton, select the "16-bit encoder"
function and define the value to be sent
Scenario control:
If a scenario should be loaded using the pushbutton, select the "Scenario load" func-
tion and define a scenario number.
5.14.2. Control modes for drive control
Standard:
If briefly operated, the drive will move incrementally or stops. If operated longer, the
drive will move up to the end position. The time difference between "short" and "long"
is set individually.
Standard inverted:
When pushed shortly, the drive moves up to the end position. When pushed for longer,
the drive moves incrementally or stops. The time difference between "short" and
"long" and the repeat interval is set individually.
Bus function
8 bit encoder
Value
0...255
Bus function
16 bit encoder
Value in 0.1
-6707600...6707600; 0
Bus function
Scenario recall
Scenario no.
0...127
Control mode
Standard
Behavior during button operation:
short = stop/increment long = Up or Down
Time between short and long
in 0.1 seconds
1...50; 10
Control mode
Standard inverted
Behavior during button operation:
short = Up or Down long = Stop/Step
Time between short and long
in 0.1 seconds
1...50; 10
Repeat the step command
for a long button press
every 0.1 s • every 2 sec; every 0.5 sec