7
Transfer protocol
Temperature Sensor KNX T-AP
• Version: 27.01.2020 • Errors excepted. Subject to technical changes.
5.
Transfer protocol
5.1.
List of all communication objects
Abbreviation flags:
C
Communication
R
Read
W Write
T
Transfer
U
Update
No.
Name
Function
DPT
Flags
0
Outside temperature reading
Input
9,001
C W
1
Inside temperature reading
Output
9,001
C R T
2
Overall temperature reading
Output
9,001
C R T
3
Min./max. temperature value request
Input
1,017
C W
4
Minimum temperature reading
Output
9,001
C R T
5
Maximum temperature reading
Output
9,001
C R T
6
Reset min./max. temperature value
Input
1,017
C W
7
Temperature sensor defect
Output
1,001
C R T
9
Temp. threshold value 1: Absolute value
Input / Output
9,001
C R W T U
10
Temp. threshold value 1: (1:+ | 0:-)
Input
1,006
C W
11
Temp. threshold value 1: Switching output
Output
1,001
C R T
12
Temp. threshold value 1: Switching output
block
Input
1,006
C W
13
Temp. threshold value 2: Absolute value
Input / Output
9,001
C R W T U
14
Temp. threshold value 2: (1:+ | 0:-)
Input
1,006
C W
15
Temp. threshold value 2: Switching output
Output
1,001
C R T
16
Temp. threshold value 2: Switching output
block
Input
1,006
C W
17
Temp. threshold value 3: Absolute value
Input / Output
9,001
C R W T U
18
Temp. threshold value 3: (1:+ | 0:-)
Input
1,006
C W
19
Temp. threshold value 3: Switching output
Output
1,001
C R T
20
Temp. threshold value 3: Switching output
block
Input
1,006
C W
21
Temp. threshold value 4: Absolute value
Input / Output
9,001
C R W T U
22
Temp. threshold value 4: (1:+ | 0:-)
Input
1,006
C W
23
Temp. threshold value 4: Switching output
Output
1,001
C R T
24
Temp. threshold value 4: Switching output
block
Input
1,006
C W