Installation and commissioning
Temperature Sensor KNX T-AP
• Version: 27.01.2020 • Errors excepted. Subject to technical changes.
2.2. Location
The sensor is designed for surface mounting. When selecting an installation location,
please ensure that the measurement results are affected as little as possible by exter-
nal influences. Possible sources of interference include:
•
Direct sunlight
•
Drafts from windows and doors
•
Warming or cooling of the building structure on which the sensor is mounted,
e.g. due to sunlight, heating or cold water pipes
•
Connection lines which lead from warmer or colder areas to the sensor
Temperature variations from such sources of interference must be corrected in the ETS
in order to ensure the specified accuracy of the sensor (temperature offset).
For outdoor installation it must be ensured that a 60 cm gap is left below the sensor in
order to prevent it from being snowed during snowfall.
The sensor must be mounted vertically. The measurement probe and the cable outlet
must point downwards.
2.3. Mounting and connection
2.3.1. Layout
Fig. 1 Opened casing, board
1
Slot for KNX te/-
2
Programming button for teaching the
instrument
3
Programming LED
4
Cable entry with threaded joint
5
Temperature sensor tip
Fig. 2 Rear view with dimensioning of
openings for mounting
1
2
3
4
5