background image

2

Description

R 24 V rain sensor 

 • Version: 03.03.2016 • Technical changes and errors excepted.

1.

Description

The 

R 24 V rain sensor 

signals precipitation (rain, snow) via a 24 V DC output.

Functions:

Heated 

precipitation sensor

 (1.2 watts): No error measurement with dew or 

mist, fast drying after the rain ends

Outlet for rain signal 

(24 V DC)

Holding time for rain signal adjustable (potentiometer in the device, 10...300 s)

1.1. Technical specification

The product conforms with the provisions of EU directives.

2.

Installation and commissioning

2.1. Installation notes

Installation, testing, operational start-up and troubleshooting should 
only be performed by an electrician.

CAUTION!

Live voltage! 

There are unprotected live components inside the device.

National legal regulations are to be followed.

Ensure that all lines to be assembled are free of voltage and take

precautions against accidental switching on.

Housing

Plastic

Colour

White / Translucent

Assembly

Surface mount

Protection category 

IP 44

Dimensions

approx. 96 × 77 × 118 (W × H × D, mm)

Ambient temperature

Operation -30…+50°C, storage -30…+70°C

Operating voltage

24 V DC

Cable cross-section

Solid conductor up to 0.8 mm²

Power consumption

60 mA

Rain sensor heater

approx. 1.2 W

"Rain" output

24 V DC

Relay capacity

5 A

Содержание 30158

Страница 1: ...ctions Item number 30158 Technical support 49 0 70 33 30 945 250 EN Elsner Elektronik GmbH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone 49 0 70 33 30 945 0 info elsner elek...

Страница 2: ...oning 2 1 Installation notes Installation testing operational start up and troubleshooting should only be performed by an electrician CAUTION Live voltage There are unprotected live components inside...

Страница 3: ...d and after conclusion of all installation and operational start up tasks and only in the surroundings designated for it Elsner Elektronik is not liable for any changes in norms and standards which ma...

Страница 4: ...wall pole mount The mount comes adhered by adhesive strips to the rear side of the housing Fasten the mount vertically onto the wall or pole Fig 2 The rain sensor must be mounted onto a ver tical wal...

Страница 5: ...installation of the weather station on a wall pole or beam pictures of sensors exem plary Example of the use of a mounting arm Due to flexible ball joints the sensor can be brought into ideal position...

Страница 6: ...ensor Version 03 03 2016 Technical changes and errors excepted 2 3 2 View of rear side and drill hole plan Langloch 7 5 x 5 mm Fig 9 a b Drill hole plan Dimensions of rear side of housing with bracket...

Страница 7: ...through the rubber seal on the underside of the housing and connect the supply voltage and the output to the terminals provided for this purpose The lead must be plugged in between the lid and circui...

Страница 8: ...t connections may destroy the sensor or con nected electronic devices After mounting remove all transport protection labels 2 5 Setting the holding time The holding time defines how long the rain sign...

Страница 9: ...e in danger e g moving windows awnings if a rain wind alarm has been triggered while cleaning Always isolate the device from the mains for servicing and cleaning The device must regularly be checked f...

Отзывы: