IOMOD
8AI
08/09/2021
V1.3 | ELSETA | Configuration over USB
14
Navigation is performed by sending digits or other symbols to a terminal. A user then proceeds by
following on-screen instructions. For example, to set baud rate, press [2] to enter Communication
settings screen; press [1] to edit; enter new configuration; press [RETURN] to save, or [ESC] to
cancel changes. When done, press [0] (exit) before disconnecting device. Default values are set by
pressing [7] on the main screen, and confirming changes [1].
It is highly advised to exit the main screen before disconnecting device
If the terminal window is closed accidentally, a user can connect the terminal program again, and
press any key on a keyboard to show the main menu again.
Modbus Main menu
Name
Function
Values
Default
Values
[1]
Slave Address
Setting Modbus
Slave address
1-247
1
[2]
Communication
settings
[1] Baud rate,
[2] Data, Stop and
Parity Bits,
[3] RS485
Terminating resistor
[1] 100 - 256000,
[2] 8 Data bits + 1/2
Stop bits,
Even/None/Odd
Parity
[3] Enabled/Disabled
[1] 9600,
[2] 8N1,
[3] Enabled
[3]
Individual channel
configuration
Channel configuration screen (see Table “Individual Channel
Configuration”)
[7]
Set Default
Settings
Sets Default
Settings
(1 to confirm, 0 to
cancel)
-
[8]
Firmware
Upgrade
Mass Storage
Device Firmware
Upgrade
(1 to confirm, 0 to
cancel)
-
[9]
Diagnostics
Raw input values
-
-
[0]
Exit
Exit and disconnect
-
-
IEC-60870-5-103 Main Menu
Menu Name
Function
Values
Default
Values
[1]
Link Address
Changing link
address
1-247
1
[2]
Baud rate, Parity
and Stop bits
[1] Set 8 Data bits +
1 Stop bit
[3] 100-256000
[3] 9600
[4] None