Device description
elrest
Automationssysteme GmbH
e
VISIO PTE715_Windows.EN
Page: 15
NOTICE
NOTICE the temperature range at a different mounting position!
In the chapter
is the range of temperature specified. It is valid for the
recommended ambient working temperature. If the device will be mounted in a diffferent
mounting position as recommended, the cooling will be affected. Please contact the elrest
service for further information.
Bring the system into a safe, de-energized state before starting installation,
disassembly or wiring of the device!
THE DEVICE MUST BE CONNECTED TO THE FUNCTIONS (FE).
All communication interfaces of the device have additionally be connected to the
function earth (FE) in the communication plug (if available).
The cable screens of the communication interfaces must be connected by the
mating connectors with the FE.
The power supply (24 VDC) must be, in accordance with its requirements (e.g.
amount of all 24 V driver outputs), adequately dimensioned and secured.
2.1.4
Mounting position
The mounting position is available in
•
Landscape, or
•
Portrait
The applicable maximum ambient temperatures must be observed for the appropriate installation
positions.
Device
Mounting position
horizontally
obliquely ± 45°
vertical
or
PTE715
0 °C … 45 °C
0 °C … 45 °C
0 °C … 45 °C
Premissible storage temperature
−20 °C ... +
70 °C
Relative humidity for operation
10 % ... 85 %
Operating height
0 m … 2000 m
Table 3:Mounting position