Please read these instructions carefully before applying power. Your attention is drawn to the fact
that the warranty is subject to the application of power sources that are within the limits specified
in this manual. This documentation was compiled with utmost care, however, we cannot guarantee
for its correctnesss in every respect. Technical details can be changed without notice, especially the
software. Please note that the described functions are only valid for units containing the software
with the version-number shown on page 1. Units with an other software number can work a little bit
different. You will find this software number on the label of the unit too.
ELREHA Gmbh
D-68766 Hockenheim,
Schwetzinger Str. 103
Telefon 0 62 05 / 2009-0 - Fax 0 62 05 / 2009-39 - [email protected]
Please note Safety Instructions !
While replacing older types please note
changed functions!
Technical Manual
5311009-50/26E
Software Vers.
from Software Vers.
1.9x
Cold Storage Controller
Type
TAR 1810-2
TAR 3810-2
TAR 5810-2
ELEKTRONISCHE REGELUNGEN GMBH
Operating Elements
Brief Description
• Cold Storage Controller with
4 relays for Solenoid Valve,
Defrost Heater, Alarm Device
and Fan
• Digital Input for door-contact
• Defrost Mode selectable,
Manual Defrost
• Defrost Termination by time /
temperature
• Fan Control by time / temperature
• Over-/Undertemperature Alarm
• Alarm Buzzer and Alarm Relay
Applications
• Cold rooms, refrigeration units,
refrigerated shelfs, etc. with
• One evaporator
• Evaporator fan
• Defrost heater,
Free-Air Defrost,
Hot Gas Defrost
Parameters
All selectable parameters hold a parameter number (e.g. P03), you will find
a listing on the next page.
Calling up and editing
Press key 'P' ...................parameter number appears
Use '
/
' .......................select desired parameter (hold key for autoscroll)
Press "P" again ...............parameter value appears
Use keys '
/
' ................adjust parameter value (hold key for autoscroll)
Press 'P' again ................value is stored, back to parameter no.
Unlock Keys / Access code
To prevent un-authorized persons from editing parameter values, there is a
locking function which allows only the most important parameters to be changed
at any time. All other parameters must be unlocked as follows:
- enter access code before programming at parameter
P53
- directly at the parameter to be changed. If a code no. is necessary the
display shows "C00". Set the matching code no. by the "
/
"-keys (70 or
80, see parameter listing) and confirm by "P".
If no key is hit for about four minutes, the access code is cancelled and the
editing function is locked automatically.
Manual Defrost
While the actual value is visible:
- Press key "
" for more than 2 seconds = Defrost ON
- Press key "
" for more than 2 seconds = Defrost OFF.
Start-up behavior
Directly after start-up the display shows "810" (controller type), after that a
display test passes.
How to find out the controller type
- Press key "P" for > 2 sec. = Display shows controller type (
810
)
- Key "
" additionally = Software version is displayed
Manual controller "wake-up"
If the controller is switched off via interface (e.g. from a PC), the display shows
"
oFF
". By holding key "
" for > 3 sec. the controller unit engage.
Reset parameters to factory settings
Switch OFF supply voltage, press and hold "P"-key, switch supply voltage
ON again. Code request "C" appears. Enter "88", confirm by "P". One by
one software version, date and "def" appear. With this, all values are reset to
factory settings.
Changes of the -2 types in comparison to the older ones
- Different terminal assignment
- Error messages now as codes + error listing
- Unlock code entry now possible at each parameter
- Storage of the last actual value while defrost
- Emergency operation while sensor failures
- 3 new parameters, new codeparameter is (P53)
Technical Data
(see parameter listing for more information)
Supply Voltage .................................................................................. see above
Power Consumption .......................................................................max. 5,5 VA
TAR 1810-2 at 12V / max. supply voltage ..........appr. 2,7 VA / 5,5 VA
Output Relays .......................................................................... 4x potential free
Contact Rating ...................................................8A cos phi = 1, 1/4 HP / 250V
Operating-/Storage Temp. ........... -10..+55°C (14..131°F)/-30..+70°C (-22..158°F)
Relative Humidity .............................................max. 80% r.H., not condensing
Temperature Sensors ................................. TF 201 (PTC) or TF 501 (Pt1000)
Display ...............................LED,7-segment,red,character height 13mm (.51)
Resolution / Accuracy ...................................................0,1°C / 0,2°F / typ. ±1K
Control-/Display Range
with TF 201 ................................................-55...+105°C / -67...221°F
with TF 5xx (depending on type) up to .. -110...+120°C / -166...248°F
Data storage parameters ....................................................................unlimited
Clock backup ....................................................typ. 10 days after mains is lost
Relay indicators .................................................................................3 mm, red
Digital input (DI) ................................................230V, max. 3mA, optocoupler
TAR 1810-2: external, potential free N/O contact
Interface ...................................................................................E-Link (RS-485)
Electrical connection ..............................................screw terminals 2,5mm (.1)
Housing / Protection
TAR 1810-2 ..........................77x 35 mm front frame, IP 54 from front
TAR 3810-2 ..................................................... for rail mounting, IP 30
TAR 5810-2 ...........................................96 x 48 mm, IP 54 from front
Accessories
(please order separately)
- Temperature sensors TF 201 or TF 501
- Transformer 107-1300-0052 (230V/12V/5VA)
All TAR types are
marked similarly
TAR 1810-2
panel mounting
12-24V AC, 18-33V DC
TAR 3810-2
rail mounting
230V AC, 50-60 Hz
TAR 5810-2
panel mounting
230V AC, 50-60 Hz
Blinking:
Night Setpoint
TAR
Increase
Values
Decrease
Values
Cooling
ON/OFF
1/
2/
Defrost
ON/OFF
Program-
ming /
Selection
P
Blinking:
Data Transmission
ELREHA
Alarm
4/
3/
Fan
ON/OFF