background image

Please read these instructions carefully before applying power. Your attention is drawn to the fact 

that the warranty is subject to the application of power sources that are within the limits specified 

in this manual. This documentation was compiled with utmost care, however, we cannot guarantee 

for its correctnesss in every respect. Technical details can be changed without notice, especially the 

software. Please note that the described functions are only valid for units containing the software 

with the version-number shown on page 1. Units with an other software number can work a little bit 

different. You will find this software number on the label of the unit too.

ELREHA Gmbh

D-68766 Hockenheim, 

Schwetzinger Str. 103

Telefon 0 62 05 / 2009-0  -  Fax 0 62 05 / 2009-39  -  [email protected]

Please note Safety Instructions !

While replacing older types please note 

changed functions!

Technical Manual 

5311009-50/26E

Software Vers. 

 

from Software Vers. 

1.9x

Cold Storage Controller

Type

TAR  1810-2

TAR 3810-2

TAR 5810-2

ELEKTRONISCHE  REGELUNGEN  GMBH

Operating Elements

Brief Description

• Cold Storage Controller with 

  4 relays for Solenoid Valve,    

  Defrost Heater, Alarm Device 

  and Fan

• Digital Input for door-contact

• Defrost Mode selectable, 

  Manual Defrost

• Defrost Termination by time /   

  temperature

• Fan Control by time / temperature

• Over-/Undertemperature Alarm

• Alarm Buzzer and Alarm Relay

Applications

•  Cold rooms, refrigeration units,  

  refrigerated shelfs, etc. with

•  One evaporator

•  Evaporator fan

•  Defrost heater, 

  Free-Air Defrost,    

 

  Hot Gas Defrost

Parameters

All selectable parameters hold a parameter number (e.g. P03), you will find 

a listing on the next page.

Calling up and editing

Press key 'P' ...................parameter number appears 

Use '

/

'  .......................select desired parameter (hold key for autoscroll)

Press "P" again ...............parameter value appears

Use keys '

/

' ................adjust parameter value (hold key for autoscroll)

Press 'P' again ................value is stored, back to parameter no.

Unlock Keys / Access code

To prevent un-authorized persons from editing parameter values, there is a 

locking function which allows only the most important parameters to be changed 

at any time. All other parameters must be unlocked as follows: 

-  enter access code before programming at parameter 

P53

-   directly at the parameter to be changed. If a code no. is necessary the    

  display shows "C00". Set the matching code no. by the "

/

"-keys (70 or  

  80, see parameter listing) and confirm by "P".

If no key is hit for about four minutes, the access code is cancelled and the 

editing function is locked automatically.

Manual Defrost

While the actual value is visible:

-  Press key "

" for more than 2 seconds = Defrost ON

-  Press key "

" for more than 2 seconds = Defrost  OFF.

Start-up behavior

Directly after start-up the display shows "810" (controller type), after that a 

display test passes.

How to find out the controller type

-  Press key "P" for > 2 sec. = Display shows controller type (

810

)

-  Key "

" additionally = Software version is displayed 

Manual controller "wake-up"

If the controller is switched off via interface (e.g. from a PC), the display shows 

"

oFF

". By holding key "

" for > 3 sec. the controller unit engage.

Reset parameters to factory settings

Switch OFF supply voltage, press and hold "P"-key, switch supply voltage 

ON again. Code request "C" appears. Enter "88", confirm by "P". One by 

one software version, date and "def" appear. With this, all values are reset to 

factory settings. 

 Changes of the -2 types in comparison to the older ones

 

 - Different terminal assignment

 -  Error messages now as codes + error listing 

 - Unlock code entry now possible at each parameter

   

- Storage of the last actual value while defrost

   

- Emergency operation while sensor failures

   

- 3 new parameters, new codeparameter is (P53)

Technical Data 

(see parameter listing for more information)

Supply Voltage .................................................................................. see above

Power Consumption .......................................................................max. 5,5 VA 

 

TAR 1810-2 at 12V / max. supply voltage ..........appr. 2,7 VA / 5,5 VA

Output Relays .......................................................................... 4x potential free

Contact Rating ...................................................8A cos phi = 1, 1/4 HP / 250V

Operating-/Storage Temp. ........... -10..+55°C (14..131°F)/-30..+70°C (-22..158°F)

Relative Humidity .............................................max. 80% r.H., not condensing

Temperature Sensors ................................. TF 201 (PTC) or TF 501 (Pt1000)

Display ...............................LED,7-segment,red,character height 13mm  (.51)

Resolution / Accuracy ...................................................0,1°C / 0,2°F / typ. ±1K  

Control-/Display Range

 

with TF 201 ................................................-55...+105°C / -67...221°F

 

with TF 5xx (depending on type) up to .. -110...+120°C / -166...248°F

Data storage parameters ....................................................................unlimited

Clock backup ....................................................typ. 10 days after mains is lost

Relay indicators .................................................................................3 mm, red

Digital input (DI)  ................................................230V, max. 3mA, optocoupler

 

 

TAR 1810-2: external, potential free N/O contact

Interface ...................................................................................E-Link (RS-485)

Electrical connection ..............................................screw terminals 2,5mm (.1)

Housing / Protection

 

TAR 1810-2 ..........................77x 35 mm front frame, IP 54 from front

 

TAR 3810-2 ..................................................... for rail mounting, IP 30 

 

TAR 5810-2 ...........................................96 x 48 mm, IP 54 from  front

Accessories 

(please order separately)

-   Temperature sensors TF 201 or TF 501

-  Transformer 107-1300-0052 (230V/12V/5VA)

All TAR types are 

marked similarly

TAR 1810-2

panel mounting 

12-24V AC, 18-33V DC

TAR 3810-2

rail mounting 

230V AC, 50-60 Hz

TAR 5810-2

panel mounting 

230V AC, 50-60 Hz

Blinking:

Night Setpoint

TAR

Increase 

Values

Decrease

Values

Cooling

ON/OFF

1/

2/

Defrost

ON/OFF

Program-

ming /

Selection

P

Blinking:

Data Transmission

ELREHA

Alarm

4/

3/

Fan 

ON/OFF

Содержание TAR 1810-2

Страница 1: ...ingle differences Changed terminal assignment Be careful while replacing older types Error messages now shown as codes and displayed as listing at P52 Unlock Acess code entry now possible at each para...

Страница 2: ......

Страница 3: ...g function is locked automatically Manual Defrost While the actual value is visible Press key for more than 2 seconds Defrost ON Press key for more than 2 seconds Defrost OFF Start up behavior Directl...

Страница 4: ...frigeration P11 88 Refrigeration Compressor Idle Time 0 59 minutes 2 minutes P12 88 Fan stop go temperature 100 C 100 C Hyst 3K fixed 50 C P13 88 Fan mode 1 2 3 4 see text 1 P14 88 Fan delay after def...

Страница 5: ...four times available P24 P27 B by digital input DI1 see chapter digital input In this case P35 will take effect as a defrost OFF time C manually P49 The defrost device is always driven from the n o co...

Страница 6: ...als 11 12 Never connect mains voltage to these terminals danger of destruction This external contact must be suitable for 5VDC 1mA Because all units are connected parallel on the data bus every unit h...

Страница 7: ...0 11 8 9 K 4 K 3 K 2 DO GND NDO 3 4 5 6 2 L N PE 1 21 K 1 20 17 18 19 F2 16 F1 97 3 81 Made in Germany ELREHA 8 35 1 38 59 2 32 26 1 02 39 1 54 For all described products there is a declaration of con...

Страница 8: ...age under unfavourable conditions The device is strongly draggled or wet After inadequate shipping conditions Never use this product in equipment or systems that are intended to be used under such cir...