Defrosting

One relay output contact is used to control a
defrosting device. Defrosting can be initiated by
the internal timer or manually. The defrost times
are set with parameters P13 thru P16.
The defrosting device is always driven from the
n/o contact of relay K2. There is no need for
interlocking the defrost with the cooling function
since with parameter P12 you select the de-
frosting mode and the controller automatically
decides on the cooling output. For information
there  is parameter P26 showing the remaining
time of the momentary defrost cycle until termi-
nation by time.

Defrosting Modes (set with P12)

Refrigeration (precondition P07=1)

1=

Heater or Free Air Defrost

Relay K2 is energized and K1 is de-energi-
zed.

2=

Hot Gas Defrost

Relays K2 and K1 are energized.

Freezing (precondition P07=2)

1=

Hot Gas Defrost

Relay K2 is energized and K1 is de-energi-
zed.

2=

Heater or Free Air Defrost

Relay K2 is energized and K1 is energized

.

Manual Defrost

Parameter  P30 allows you to start a defrost
cycle with the "

ñ

" key, unless the sensor is

already above  termination temperature.

Defrost Termination

There are three ways for terminating a defrost
cycle:

1st:

thermal termination.
Whenever the evaporator sensor tem-
perature (P02) is warmer than the tem-
perature limit set with parameter P11,
defrosting is terminated.

2nd:

termination by (safety) time.
The time set with parameter P17 is the
maximum time a defrost cycle can last
before it is terminated automatically.

3rd:

manual terminating.
Under parameter P30 you can termina-
te a defrost cycle by pressing the "

ò

"

key.

Evaporator Fan Control

The K3 relay can be used for controlling the fan,
if it is not used for alarm purposes (see P25).
Different modes of fan operation can be selec-
ted with parameter P20.

Fan  Modes

1 = Fan runs when compressor output (K1) is

on. After defrosting,  the fan output is OFF
until the programmed Fan Delay Time (P21)
is complete.

.

2  = Fan runs continously, except during defrost

and Fan Delay Time (P21).

3 = Fan runs when the compressor output (K1)

is on, and during defrost. There is no fan
delay time.

A thermostatic fan control is always available.
Fan runs when sensor temperature (P02) is
below setpoint for the programmed Fan Start/
Stop Temperature (P19).
If you don't need this function, set parameter
P19 to the highest value.
The fan is always run from the n/o contact of
relay K3.
When fan delay is active, parameter P28 shows
the remaining time.

Содержание TAR 1310

Страница 1: ...ess code is cancelled and the editing function is locked automatically ELEKTRONISCHE REGELUNGEN GMBH General The TAR x31x series controller was designed for controlling refrigeration and freezer devices with all their necessary functions There are three standard relay outputs available and all operation is made from the front Features Following functions and features are included in the standard t...

Страница 2: ...about 10 days on power failure Because the display has three digits only the time value comes in the following for mat Function Display All temperature values can be displayed in C or F Parameter P08 allows toggling these two display modes Temperature Control The controller compares the actual room tem perature with the setpoint P03 and according to the deviation energizes or de energizes re lay K...

Страница 3: ... temperature Defrost Termination There are three ways for terminating a defrost cycle 1st thermal termination Whenever the evaporator sensor tem perature P02 is warmer than the tem perature limit set with parameter P11 defrosting is terminated 2nd termination by safety time The time set with parameter P17 is the maximum time a defrost cycle can last before it is terminated automatically 3rd manual...

Страница 4: ...us P14 Defrost time 2 000 235 00 00 a m 11 50 p m Aus P15 Defrost time 3 000 235 00 00 a m 11 50 p m Aus P16 Defrost time 4 000 235 00 00 a m 11 50 p m Aus P17 Defrost safety Time 1 99 minutes 30 minutes P18 Cooling delay after defrost 0 99 minutes 0 minutes P19 Fan Stop Go Temperature total control range 0 C P20 Fan Mode 1 2 3 see text 1 P21 Fan delay after defrost 0 30 minutes 3 minutes P22 Alar...

Страница 5: ...ay reads the temperature of the control room sensor After you have punched in the access code see chapter unlock keys you programm the configuration of the controller to suit your application switching mode parameter P07 display mode P08 defrost method P12 evaporator fan mode P20 and or the alarm mode P25 Thebasicsetupiscompletenow and you can edit the setpoints delay times etc If for any reason t...

Страница 6: ...t K1 40 29 64 70 55 Dimensions and Wiring TAR 4310 ELREHA P E 8 Fühler gem 3 K1 Schließer 7 K3 Ventilator oder Warnen 4 K1 Öffner 5 K1 Wurzel 6 K2 Abtauen 1 Netz L 2 Netz N 10 Abtaufühler 9 Regelfühler PE mains phase mains neutral relay K1 N O relay K1 N C relay K1 common relay K2 N O relay K3 N O sensor common control sensor evaporetor sensor ...

Страница 7: ...l entfernen Klappe öffnen und Schraube lösen 136 ELREHA 87 5 P TAR 2000 34 Bottom Case Mounting Holes 10 evaporator sensor F2 9 control sensor F1 8 sensor common 7 K3 fan or alarm relay N O 6 K2 defrost relay N O 5 K1 control relay N O 4 common K1 K2 K3 3 K1 control relay N C 2 mains phase 1 mains neutral ...

Страница 8: ...lation with IEC 1000 4 3 is based on test results which are located on site at the manufacturer EG Statement of Conformity We state the following When operated in accordance with the technical manual the criteria have been met that are outlined in the guidelines of the council for alignment of statutory orders of the member states on electro magnetic consistency 89 336 EWG This declaration is vali...

Отзывы: