TAA 2140, TAA 22140

Parameters
No. 

Parameter 

Range 

Factory set 

P01

  .... Actual value signal input 1 ..................... -50...300 .................................................................................................................display only 

P02

  .... Actual value signal input 2 ..................... -50...300 .................................................................................................................display only 

P03

  .... Display Mode ......................................... 0= without decimal place, with noise filter ..............................................................2

 

 

1= with decimal place and noise filter

 

 

2= with decimal place, without noise filter

P04

  .... Alternating Mode .................................... 0= not alternating ...................................................................................................0

 

 

1= every 16 seconds the display changes from P01 to P02. 

In doing so, 

 

 

the parameter number appears always for a short time

P05

  .... Display with 10V at signal input 1  ......... -50...300 .................................................................................................................100

P06

  .... Display with 0V at signal input 1 ............ -50...300 .................................................................................................................-50

P07

  .... Display with 20mA at signal input 2 ....... -50...300 .................................................................................................................100

P08

  .... Display with 4mA at signal input 2 ......... -50...300 .................................................................................................................0

P09

  .... Correction value for signal input 1 ......... ± 10.0 .....................................................................................................................0

P10

  .... Correction value for signal input 2 ......... -10,1...+10.0 (With -10.1, this input is switched off, P02 changes to "oFF") ..........0

P11

  .... Alarm upper limit signal of input 1 .......... -50...+300°C ...........................................................................................................+300

P12

  .... Alarm lower limit signal of input 1 .......... -50...P07 ................................................................................................................-50

P13

  .... Alarm upper limit signal of input 2 .......... -50...+300°C ...........................................................................................................+300

P14

  .... Alarm lower limit signal of input 2 .......... -50...P09 ................................................................................................................-50

P15

  .... Alarm delay ............................................ 1...99 minutes ........................................................................................................60 minutes

P16

  .... Alarm repetition time .............................. 0...99 minutes (0 = no alarm repetition after a reset) .............................................15 minutes

P17

  .... Remaining time Alarm/Reset .................................................................................................................................................display only

P18

  .... Access Code .......................................... 88 ...........................................................................................................................00

Liste des paramètres
Nr. 

Paramètre 

Plage 

Val. usine 

 

P01

  .... Mesure entrée 1 ..................................... -50...300 .................................................................................................................--   

 

P02

  .... Mesure entrée 2 ..................................... -50...300 .................................................................................................................--   

P03

  .... Mode d'affichage .................................... 0= sans 0.1 avec filtrage ........................................................................................2

 

 

1= avec 0.1 avec filtrage

 

 

2= avec 0.1 sans filtrage

P04

  .... Mode display .......................................... 0= Affichage normal ...............................................................................................0

 

 

1= toutes les 16 secondes, l'afficheur permute entre P01 et P02, pour 

 

 

visualiser 2 mesures en même temps

P05

  .... Affichage entrée 1 pour 10V .................. -50...300 .................................................................................................................100

P06

  .... Affichage entrée 1 pour 0V .................... -50...300 .................................................................................................................-50

P07

  .... Affichage entrée 2 pour 20mA ............... -50...300 .................................................................................................................100

P08

  .... Affichage entrée 2 pour 4mA ................. -50...300 .................................................................................................................0

P09

  .... Correction mesure entrée 1 ................... ± 10.0 .....................................................................................................................0

P10

  .... Correction mesure entrée 2 ................... -10,1...+10.0 (en réglant jusqu'à -10.1, l'afficheur ..................................................0

 

 

indique "oFF" et l'entrée est inhibée)

P11

  .... Seuil haut alarme entrée 1 ..................... -50...+300°C ...........................................................................................................+300

P12

  .... Seuil bas alarme entrée 1 ...................... -50...P07 ................................................................................................................-50

P13

  .... Seuil haut alarme entrée 2 ..................... -50...+300°C ...........................................................................................................+300

P14

  .... Seuil bas alarme entrée 2 ...................... -50...P09 ................................................................................................................-50

P15

  .... Retard d'alarme ..................................... 1...99 minutes ........................................................................................................60 minutes

P16

  .... Temps avant répétition alarme ............... 0...99 minutes (0=pas de répétition alarme après acquittement) ...........................15 minutes

P17

  .... Temps restant avant alarme .................. affichage seul.

P18

  .... Entrée code de déverrouillage ............... 88 ...........................................................................................................................00

We state the following: When operated in accordance with the technical manual, the criteria have been met that are outlined in the guidelines of the 

council for alignment of statutory orders of the member states on EMC-Directive (2004/108/EC) and the Low Voltage Directive (LVD 2006/95/EC). 

This declarations are valid for those products covered by the technical manual which itself is part of the declaration. To meet the requirements, the 

currently valid versions of the relevant standards have been used
This statement is made from the manufacturer / importer 

by: 

ELREHA Elektronische Regelungen GmbH 

Werner Roemer, Technischer Leiter, 

Technical Director 

D-68766 Hockenheim 

 

 

 

 

 

 

www.elreha.de   

Hockenheim

.............

15.04.2009

.......................................................

(Name / Anschrift /

 name / adress

Ort/

city 

Datum/

date

 

 

Unterschrift/

sign

EG-Statement of Conformity

Parameterliste
Nr. 

Parameter 

Bereich 

Werkseinst.    

P01

  .... Istwert 0-10V-Eingang (F1) .................... -50...300 .................................................................................................................nur Anzeige   

P02

  .... Istwert 4-20mA-Eingang (F2) ................. -50...300 .................................................................................................................nur Anzeige 

P03

  .... Anzeigemodus ....................................... 0= ohne Nachkommastelle mit Störungsfilter ........................................................2

 

 

1= mit Nachkommastelle und Störungsfilter

 

 

2= mit Nachkommastelle ohne Störungsfilter

P04

  .... Display Modus ....................................... 0= normale Anzeige ...............................................................................................0

 

 

1= alle 16 Sekunden wird von P01-Anzeige auf P02-Anzeige gewechselt. 

 

 

Dazu wird jeweils kurz die Parameternummer eingeblendet.

P05

  .... Anzeige bei 10V an Signaleingang 1 ..... -50...300 .................................................................................................................100

P06

  .... Anzeige bei 0V an Signaleingang 1 ....... -50...300 .................................................................................................................-50

P07

  .... Anzeige bei 20mA an Sign.eingang 2 .... -50...300 .................................................................................................................100

P08

  .... Anzeige bei 4mA an Sign.eingang 2 ...... -50...300 .................................................................................................................0

P09

  .... Korrekturwert Eingang F1 ...................... ± 10.0 .....................................................................................................................0

P10

  .... Korrekturwert Eingang F2 ...................... -10,1...+10.0 (Mit -10.1 ist dieser Fühler abgeschaltet, Anzeige wechselt  ............0

 

 

dann auf "oFF")

P11

  .... Alarm-Obergrenze Eingang F1 .............. -50...+300°C ...........................................................................................................+300

P12

  .... Alarm-Untergrenze Eingang F1 ............. -50...P07 ................................................................................................................-50

P13

  .... Alarm-Obergrenze Eingang F2 .............. -50...+300°C ...........................................................................................................+300

P14

  .... Alarm-Untergrenze Eingang F2 ............. -50...P09 ................................................................................................................-50

P15

  .... Alarmverzögerung ................................. 1...99 Minuten ........................................................................................................60 Minuten

P16

  .... Alarmquittierungszeit ............................. 0...99 Minuten (0=keine Alarmwiederholung nach Quittierung) .............................15 Minuten

P17

  .... Restlaufzeit Alarm/Quittierung ...............................................................................................................................................Nur Anzeige

P18

  .... Zugangscode ......................................... 88 ...........................................................................................................................00

original set up:  14.4.09, tkd/jr 

checked: 15.4.09, ek/ha  

approved:  15.4.09, mkt/sha 

transl.(E):  

korr: 3.9.15, tkd/jr