905U-L Wireless I/O Installation Manual
905U-L Wireless I/O
Page 22 of 40
Version 1.9
Inputs and outputs
The units have the following inputs and outputs:
Input/output
905U-L-T
905U-L-R
Description
For more
information, see
…
Digital inputs
2
Suitable for Voltage free contact,
NPN transistor, 0-5V signal.
Relay outputs
3
250VAC 1A / 30VDC 1A.
Relay outputs
Important Information
on page 24.
Status outputs
2
2
Max 30VDC, 500 mA. Indicate
module status, communication
failure and local setpoint status.
Analog inputs
1
4-20 mA with over-range and
under-range.
0-10 mA with over-range.
Analog input on page
26.
+24V Loop supply
1
Provides power for 1 external
current loop (up to 35 mA).
Installing the power
supply on page 21.
Analogue setpoint
1
Allows discrete setpoint to be
controlled from analog input.
Threshold adjustable via rotary
switch.
Refer to the
User
Manual
.
Thermocouple /
millivolt input
1
Provides measurement of E, J, K,
T type Thermocouple, millivolt
signals and user-defined
thermocouple types.
Thermocouple input
on page 29
Thermocouple
setpoint
1
Lets you control discrete setpoint
from thermocouple with threshold
adjustable via rotary switch.
Refer to the
User
Manual
.
Pulse inputs
2
Up to 10Hz.
Pulse input on page
30.
Analog output
1
0-22 mA, suitable for loop
powered, floating input or single-
ended input device.
For more information, see the next sections.