Important Notices
ELPRO products are designed to be used in industrial environments by experienced industrial engineering personnel with adequate knowledge of safety design considerations. ELPRO radio products can be used unprotected license-free radio bands with
radio noise and interference. The products are designed to operate in the presence of noise and interference, but in an extreme case radio noise and interference can cause product operation delays or operation failure. Like all industrial electronic
products, ELPRO products can fail in a variety of modes due to misuse, age, or malfunction. We recommend that users and designers design systems using design techniques intended to prevent personal injury or damage during product operation and
provide failure tolerant systems to prevent personal injury or damage in the event of product failure. Designers must warn users of the equipment or systems if adequate protection against failure has not been included in the system design. Designers must
include this Important Notice in operating procedures and system manuals. These products should not be used in non-industrial applications, or life-support systems, without consulting ELPRO first. A radio license is not required in some countries,
provided the module is installed using the aerial and equipment configuration described in the Installation Guide. Check with your local distributor for additional information on regulations. Operation of unlicenced equipment is authorized by the radio
frequency regulatory authority in your country on a non-protection basis. Although all care is taken in the design of these units, there is no responsibility taken for sources of external interference. Systems should be designed to be tolerant of these
operational delays. To avoid the risk of electrocution, the aerial, aerial cable, data/IO cables and all terminals of the module should be electrically protected. To provide maximum surge and lightning protection, the module should be connected to a suitable
ground and the aerial, aerial cable, IO, data cables and the module should be installed as recommended in the Installation Guide. To avoid accidents during maintenance or adjustment of remotely controlled equipment, all equipment should be first
disconnected from the module during these adjustments. Equipment should carry clear markings to indicate remote or automatic operation. For example:
“This equipment is remotely controlled and may start without warning. Isolate at the switchboard
before attempting adjustments.
” The equipment operates unlicensed radio frequencies, proprietary protocols to communicate over the radio, cyber security features and encryption. Nevertheless, if your system is not adequately secured, third parties may
be able to gain access to your data or gain control of your equipment via the radio link. Before deploying a system, make sure that you have carefully considered the security aspects of your installation and read the user documentation.
Proper Use
Any unauthorized modifications to or use of this equipment outside its specified mechanical, electrical, or other operating limits may cause personal injury and/or property damage, including damage to the equipment. Any such unauthorized modifications:
(1)
constitute “misuse” and/or “negligence” within the meaning of the product warranty, thereby excluding warranty coverage for any resulting damage; and (2) invalidate product certifications or listings.
POWER SUPPLY
BAT (11-15Vdc):
Internal battery if fitted or connect
external battery with 5A fast blow fuse.
GND:
Power supply system ground
SOLAR+ (17-30Vdc):
5-30W solar panel or external
24W power supply to power unit or charge internal/
external battery (ONLY Lithium Iron Phosphate or SLA).
GND:
Solar or external power supply common/Ground
connection
4-20mA or 0-10Vdc ANALOG INPUTS
GND:
Analog input ground
AIN1 +/-:
Externally powered 4-20mA input
0-10Vdc Voltage Input
Loop powered 4-20mA. 30Vdc max
+24 LOOP:
4-20mA Loop or sensor power supply.
Switched on for warmup plus sample period. 50mA
MAX
DISCRETE INPUTS
GND:
Discrete inputs ground
DIO1:
ON/OFF or pulse
DIO2:
ON/OFF or pulse
DIO3:
ON/OFF input
DIO4:
ON/OFF input
Note:
Discrete input DRY contact close to ground
NOTES:
All I/O connections must be SELV
Solar and external power supply/ battery charger:
(A) 17-30Vdc Supply or internal battery charger input, 2A
NEC Certified Class 2
(B) Solar panel to charge internal/external 12V battery
(30W, charge current 2.0A MAX)
(C) 11-15Vdc battery supply input
(D) DO NOT connect external supply to BAT terminal with
internal battery option connected.
Environmental Specification:
Ingress Protection
IP66
Operating Temperature ext supply -40 to 70°C (-40 to 158°F)
LFP rechargeable battery
-20 to 60°C (-4 to 140°F)
LiP non-rechargeable battery
-40 to 70°C (-40 to 158°F)
Altitude
2000m
Pollution Degree
4
Internal Humidity
Max 95% non-condensing
©
ELPRO Technologies Pty. Ltd.
2021 Rev. 1.0
+
_
11-15V
Battery
17-30V
Solar or
Supply
Voltage
Free
Contact
Transistor
Switch
Device
G
N
D
D
IO
1
D
IO
2
D
IO
3
D
IO
4
G
N
D
TTL
CMOS
Output
G
N
D
S
O
L
A
R
+
G
N
D
V
B
A
T
Loop powered
sensor
+
-
mA
G
N
D
- +
+
2
4
L
O
O
P
AI1
Externally powered
Current Sensor
Or a Voltage I/P
+
-
G
N
D
- +
+
2
4
L
O
O
P
AI1
5A
Fuse