background image

925U-2 wireless mesh networking I/O and gatewayinstallation guide 

  

  

Install Guide 

925U-2

Effective Sept 2022

ELPRO Technologies

29 Lathe St

Virginia, QLD 4014

Australia

www.elprotech.com

Telephone: 

61 7 3352 8600

ELPRO Technologies Inc

2028 East Ben White Blvd,

#240-5656 Austin, TX 78741-6931

USA

Telephone: 

USA: +1 855 443 5776

ELPRO is a registered trademark.  

All other trademarks are property of their respective owners.

© 2022 ELPRO

All Rights Reserved

NOTE

All connections must be SELV <50 Vac and <60 Vdc.

The following illustrations show the ports on the 925U 2.

PWR
RF

232

485

LED Indicator 
Lights

I/O Connectors

RJ-45 Ethernet Port

(connects to hub or switch)

USB Port RS-232 Port

ETHERNET

USB

RS232

SUPPLY

+

-

GND BAT SUP SUP

+

B

A

-

+

Power supply wiring

The ground (GND) and “SUP –“ 

terminals are connected internally to 

the ground terminal.
Connect the screw terminal on 

the end plate to ground for surge 

protection.

Expanson I/O power and RS-485 serial connection

An on-board RS-485 terminating 

resistor provides line 

attenuation for long runs.
Place terminating resisters at 

each end of the RS-485 cable.

Configuration switches

Use the DIP switches in the side 

access panel to select analog input 

voltage and current, external boot, 

and default configuration settings.

DIP

DESCRIPTION

1

AI3 current/voltage

2

AI3 current/voltage

3

AI4 current/voltage

4

AI4 current/voltage

5

Unused

6

Enables default configuration

Input and output connections

The digital input/output channels can be wired as inputs or outputs.

Digital input

Digital output

Transistor

Switch

Device (NPN)

Voltage-free Contact

TTL CMOS

Output

D1

D3 D4 D5 D6 D7 D8 GND+24V

D2

DC Load

200mA max

+

D1

D3 D4 D5 D6 D7 D8

GND +24V

D2

30V DC max

Differential current inputs (Al1, Al2)

Single-ended current input (Al3, Al4)

mA

Loop-Powered

Sensor

Exernally 

Powered

Sensor

Power Supply

D7 D8

GND +24V

AI1

+

AI1

_

AI2

+

AI2

_ AI3 AI4

AO1

+

AO2

+

GND +24V

mA

Loop-Powered

Sensor

Power Supply

Externally

Powered

Sensor

DIP Switch Setting

for Current IP

GND +24V

AI1

+

AI1

_

AI2

+

AI2

_ AI3 AI4

AO1

+

AO2

+

GND +24V

1     2     3    4     

5    6

ON

Analog output

  Single-ended voltage input

AI

PLC

COM

AI1

+

AI1

_

AI2

+

AI2

_ AI3 AI4

AO1

+

AO2

+

GND +24V

0–25V 

Sensor

0–5 Vdc 

Sensor

+24V

AI1

+

AI1

_

AI2

+

AI2

_ AI3 AI4

AO1

+

AO2

+

GND +24V

V

V

DIP Switch Setting

for Voltage IP

ON

1     2     3    4     

5    6

ETHERNET

USB

RS232

B

A

-

+

115S-xx

115S-xx

RS-485

B

A

B

A

B

A

-

+

-

+

USB

RS232

SUPPLY

+

-

GND BAT SUP SUP

+

15-30 Vdc

Supply

3A Fuse 

Optional
10.8–15 Vdc
Lead Acid 
Battery

+

USB Host

Configuration 

Switches

Side 

Access 

Panel

Отзывы: