Содержание R 1120

Страница 1: ......

Страница 2: ...t is not permitted to connect the grounds of the sensor inputs and logic outputs with each other Separate installation of controller and inductive loads is recommended Interference from contactor coil...

Страница 3: ...elay alarm 3 output 4 Connection Diagram Pt 100 RTD OUT 2 OUT 1 OUT 3 2 wire cooling or heating or alarm 2 cooling alarm 3 relay relay relay 1 2 3 4 5 6 7 8 9 10 11 TC bistable N L AC Voltage Output P...

Страница 4: ...and edit mode Long press This is used to switch between different operating levels If the controller is in the edit mode other levels cannot be reached Parameter mode In the operating parameter and c...

Страница 5: ......

Страница 6: ...2 212 F P2C Pt 100 100 200 C P2F Pt 100 148 392 F P4C Pt 100 0 400 C ex works P4F Pt 100 32 752 F P8C Pt 100 0 800 C L4C T C Fe CuNi L 0 400 C L4F T C Fe CuNi L 32 752 F L8C T C Fe CuNi L 0 800 C J8C...

Страница 7: ...f the limit comparator with displayed relative to the setpoint start up suppression is activated when the The selected value is effective below and above controller is first switched on It is only de...

Страница 8: ...t on off 6 limit comparator on off on 7 limit comp with start up suppression off on off LOC Adjustment lock OFF no adjustment lock ex works P C parameter and configuration levels locked n SP all param...

Страница 9: ...mited ratio Warning The output ratio limitation does not work during auto tune 1 P OUT 1 Xp OFF 0 1 99 9 ex works 3 0 prop band P if Xp OFF the next parameter to follow is 1Sd control sensitivity OUT...

Страница 10: ...helpful to reduce the switching frequency between the heating and cooling outputs if this is too high Simultaneous activation of heat and cool outputs is not possible 2 P OUT 2 Xp cooling OFF 0 1 99 9...

Страница 11: ...ing Opt is shown in the display alternating with the setpoint value Using the heat cool controller the temperature drop will be accelerated by switching on the cooling for a short duration After havin...

Страница 12: ...9 C F OFF 19 9 19 9 C F limit comparator set point dependent OFF 1 199 C F OFF 0 1 19 9 C F limit contact process value dependent OFF range bottom range top Alarm 2 is only available if the controller...

Страница 13: ...set to OFF the controller switches to stand by The process display then shows OFF All main outputs are switched off and the alarm is deactivated All parameters can be displayed and altered during stan...

Страница 14: ...250 V AC max 3 A resistive load OUT 3 Relay n o contact max 250 V AC max 3 A resistive load 7 Segment Display Process 10 mm red Set 10 mm red Data protection EAROM CE mark EMC 2004 108 EC EN 61326 1...

Страница 15: ...d Check sensor and cable sensor defect C A2 configuration of Alarm 2 is switched off Set parameter C A2 C A3 configuration of Alarm 3 is switched off Set parameter C A3 Er O Self tuning error Extingui...

Страница 16: ...Manual R1120 X0 00 X_EN Release 1 04 Elotech GmbH Page 16 16...