Art.-Nr./Art. No./Réf./N° art/N° art.: 9010007B01M

  Version

: 1.2

Date:

 21.03.2017     

   

1/6

1

In these operating instructions

The following standard models are described:
- 470EFR2D12K_

SIL2/PLd with 2 safety outputs

- 470EFR3E12K_

SIL3/PLe with 2 safety outputs

- 470EFR3E11K_

SIL3/PLe with 1 safety output

The selected configuration can be obtained from the data sheet.
The person installing the safety control unit is to be provided with the operating
instructions.
The operating instructions and the data sheet must be kept in a legible condi-
tion and in an accessible location.
Meaning of the symbols used:    

2

Designated use

The safety control unit is an integral part of the overall system or machine and
serves for performing safety-related functions.
This is done by monitoring signals by e.g. safety sensors, emergency-stop
buttons, position switches, no-contact protective equipment BWS. The
product must exclusively be applied in accordance with the descriptions
below.

3

Safety instructions

4

Warning against misuse 

5

Exclusion of liability

No liability shall be accepted for damage and operational faults caused by a failure
to observe these operating instructions. All further liability of the manufacturer is
excluded in the case of damage caused by the use of replacement and accessory
parts that have not been authorised by the manufacturer.
No unauthorized repairs, conversions and changes are permitted for reasons of
safety and the manufacturer shall not be liable for damage resulting therefrom.

Warning

Failure to observe this warning may result in faults or malfunc-
tions.
Failure to observe this warning may result in personal injury
and/or damage to the machine.

- Ensure that the safety control unit is only put into operation by

specially-trained authorised personnel.

- Only install and put the device into operation once you have

read and understood the operating instructions and are familiar
with the applicable regulations on occupational safety and
accident prevention.

- Ensure that the corresponding fuses (see technical specifica-

tions) are used. Never bypass or repair fuses.

- Ensure that the safety control unit is only used to protect against

dangers.

- Ensure that all safety requirements applying for the machine in

question are observed.

- Ensure that all applicable European directives and national

laws/directives are observed.

- Ensure that the control output is only used for displaying the

operational status of the safety control unit.

- There are no known residual risks if all of the information

contained in these operating instructions is complied with.

- In case of incorrect or unintended use or manipulation, the use

of the safety control unit does not exclude risks to persons or
damage to machine or system components.
Please also observe the relevant information stipulated in the
ISO 14119 standards.

- Ensure that no current or voltage peaks which are higher than

the specified electrical data of the safety control unit are caused
by external components. Current or voltage peaks may for
example be generated through capacitive or inductive loads.

- An exceeding of the electrical data of the safety control unit (e.g.

in the event of incorrect wiring or short-circuits) may cause
irreparable damage to the unit. Non-compliance may result in
reduced service life.

6

Function

2 safety inputs, that can be connected differently, connect the safety resp. the
control outputs depending on the configurable, logical connection. In addition,
there is an input available for reading external contactors and start buttons.
The details of configuration can be obtained from the data sheet.

Configuration possibilities

On our website www.elobau.com you will find the eloFlex Configurator, which
offers a step-by-step guide to derive your required configuration. Clicking on
underlined terms and functions serves to open an explanatory window to
explain the items in more detail.
The micro-controller controlled safety control unit can be delivered with the
following configuration possibilities.
Each component can be individually adjusted.

Upon connection of a sensor, the (+) potential must be disconnected from
terminals 5 and 9.
Upon selection of OSSD at the safety input, a sensor with cross-short detection
must be used or any errors resulting from cross-shorts must be ruled out.

Safety input 1-2

NO/NO (-/+)

e.g. protective door

NO/NC (-/+)

e.g. protective door

NC/NC (-/+)

Emergency-stop push-button

OSSD (safe semiconductor)

 

(+/+)

only safe sensors with PNP outputs, 
e.g. light grids

Maximum one external contactor input can be assigned to one safety output.

* When selecting the logic operator, ensure that the resulting function fulfils the
specified safety function and corresponds to the specified properties.

External contactor/start

automatic

Automatic start/restart with HIGH level

manual

Release at rising flank

monitored

Release at falling flank

Safety output 1-2

Input

Logic *

Switch on/switch 

off delay in s

External monitoring

Safety input 1

AND

t

ON





s

___

t

OFF





s

Contactor/
start 1

Safety input 2

OR

NAND

NOR

XOR

XNOR

NOT

Two-hand control 1 + 2

* The control output is switched on after initialization.
There is no input assignment for the selection of BTR, fault or safety output.
The switch on/switch off delay of the outputs can be chosen from 0.0 s until
99.9 s in 0.1 second steps.

Control output

Input

Logic

Switch on/switch off 

delay in s

AND

t

ON





s

___

t

OFF





s

Safety input 1

Safety input 2

OR

NAND

NOR

XOR

XNOR

NOT

BTR*

FAULT

as safety output 1

as safety output 2

Содержание 470 EFR 2D1 2K

Страница 1: ...e use of the safety control unit does not exclude risks to persons or damage to machine or system components Please also observe the relevant information stipulated in the ISO 14119 standards Ensure that no current or voltage peaks which are higher than the specified electrical data of the safety control unit are caused by external components Current or voltage peaks may for example be generated t...

Страница 2: ...oring Operating voltage 1 13 Control output 14 Not suitable for safety functions Switching dependent on Safety input 1 2 Logic Switch on switch off delay optional 1 3 5 4 6 2 LED 1 Operability Ready LED 2 Fault Error LED 3 Safety input 1 I 1 LED 4 Safety input 2 I 2 LED 5 Safety output 1 O 1 LED 6 Safety output 2 O 2 10 Commissioning In arbitrary order Damp safety sensors Apply operating voltage m...

Страница 3: ...rt and storage temperature 40 85 C 40 85 C Electrical properties eloFlex 470EFR2D eloFlex 470EFR3E Operating voltage fuse fast acting 1 A Safety output fuse 3 A Operating voltage 24 V DC 10 Max current consumption 200 mA Status display 6 x LED Max switching voltage of safety outputs 1 2 250 V AC 30 V DC Max switching current of safety outputs 1 2 3 A Max switching capacity of safety outputs 1 2 75...

Страница 4: ...rating time of sensor contacts Actuation typical 3 s Operating time of 2 hand control 0 5 s Max response time 50 ms 1 Additional safety related characteristics upon request 2 Assumptions for calculation in accordance with IEC TR 62380 daily cooling to 20 C followed by continuous operation at 55 C and max 10 switching cycles per hour Terminal connections eloFlex 470EFR2D eloFlex 470EFR3E Operating ...

Страница 5: ...Art Nr Art No Réf N art 9010007B01M Version 1 2 Date 21 03 2017 5 6 Mechanical design 100 120 22 5 Schematic diagram Attention Example of circuit ...

Страница 6: ... für Sensoren mit Schließer Schließer oder Schließer Öffner Kontaktsystem configurable safety related system for sensors with 2 normally open or normally open normally closed contact system elobau Artikel Nr elobau item no 470 EFR 2D1 2K 470 EFR 3E1 2K 470 EFR 3E1 1K Einschlägige EG Richtlinien Relevant EC Directives Maschinenrichtlinie 2006 42 EG EMV Richtlinie 2014 30 EU Machinery Directive 2006...

Отзывы: