17
2.4 Connections
To connect the
ElNet
Energy Powermeter
All Connections are made via terminal connector plugs (Voltage
input, Power Supply, etc.).
Recommended max. tightening torque for the connector screws is
0.5 Nm.
The CT cores of the
ElNet
Energy Powermeter
a
re located
internally in the instrument and the lead from the leg of the
external Current Transformer must be connected to the correct
terminal connector in order to maintain the correct direction.
NOTE!
Ensure all the connections to the leads of the current
transformer wiring is secure and there is no mechanical
strain on the wire
Connect the lead from side “
L
” to the terminal connector L at the
relevant phase, than connect the lead from side “
K
” to the
terminal connector K at the same phase, of the
ElNet
Energy
Powermeter
.