ELMON rail 41-822 / ELMON rail 41-322
Safety relais
13
10. Commissioning and function testing
Following a corresponding connection of all electrical connections and switching on the supply voltage, the
system / machine must be checked for correct functionality.
After successful commissioning the
13
and
24
safety output is driven (relay contact “closed“). An operation
of the sensor causes an opening of the
13
and
24
relay contact.
The signaling relay (
31
32
connection) switches in accordance with the present DIP switch position. This is
indicated by means of the yellow
AUX1
LED
The safety system must be inspected by competent specialists at suitable intervals. The check must be
documented in a way that allows it to be traced at any time. The requirements of the system / machine
manufacturer are to be taken into account and observed.
Commissioning and functional testing, must be performed by authorized and professional trained staff.
11. Fault diagnosis
If the supply voltage is correctly wired and applied, only the green
Power
LED may be lit up. If the red LED
illuminates, there is a fault in the system which can be delimited by means of the LED.
LED
Fault
Fault removal
green
Power
LED
does not light up
Supply voltage is missing,
too low or
incorrectly connected.
Check connections and supply voltage:
- 230 V AC (or 120 V) at terminals
A1 A2
or
- 24 V AC/DC at terminals
B1 B2
Tolerance range: ±10%
green
Power
LED
flashes cyclically
(pulse output)
Internal fault is indicated
by the number of pulses.
See -> signal displays
red
CH1
LED
lights up
The corresponding sensor
is recognized
as being operated.
- Check the connections of the corresponding sensors
(squeezed or brittle supply lines, etc.)
- Check signal sensor *
red
CH1
LED
fast flashing
Sensor circuit interrupted,
sensor not connected,
defectively connected or
defective.
- Check the connections of the corresponding sensors
(squeezed or brittle supply lines, etc.)
- Check signal sensor *
red
CH1
LED
slow flashing
Fault self-retaining
Carry out manual reset
* If the fault is not found in the wiring, the function of the electronic system can be checked by applying
a resistance of 8.2 kΩ to the sensor-input on the switching device. Subsequently, if the electronics work
perfectly, the sensor must be checked by means of an ohmmeter. For this purpose, the connection of
the sensor to the switching device must be separated and connected by means of an ohmmeter. In the
case of a non-operated sensor the resistance must be 8.2 kΩ ± 500 Ω. If the sensor is operated, the
resistance must not exceed 500 Ω.
12. Decommissioning and disposal
The products manufactured by ASO are exclusively intended for commercial use (B2B). At the end of use, the
products must be disposed of according to all local, regional and national regulations. ASO is also happy to
take back the products and disposes of them properly.
Содержание 41-322
Страница 17: ...17 Notes ELMON rail 41 822 ELMON rail 41 322 Safety relais ...
Страница 18: ...18 Notes Safety relais ...
Страница 19: ...19 Notes ELMON rail 41 822 ELMON rail 41 322 Safety relais ...