ELMON 41-322 Скачать руководство пользователя страница 13

ELMON rail 41-822 / ELMON rail 41-322

Safety relais

13

10. Commissioning and function testing

Following a corresponding connection of all electrical connections and switching on the supply voltage, the

 

system / machine must be checked for correct functionality.
After successful commissioning the 

13

 and 

24

 safety output is driven (relay contact “closed“). An operation

 

of the sensor causes an opening of the 

13

 and 

24

 relay contact.

The signaling relay (

31

 

32

 connection) switches in accordance with the present DIP switch position. This is

 

indicated by means of the yellow 

AUX1

 LED 

The safety system must be inspected by competent specialists at suitable intervals. The check must be

 

documented in a way that allows it to be traced at any time. The requirements of the system / machine

 

manufacturer are to be taken into account and observed.
Commissioning and functional testing, must be performed by authorized and professional trained staff.

11. Fault diagnosis

If the supply voltage is correctly wired and applied, only the green 

Power

 LED may be lit up. If the red LED

 

illuminates, there is a fault in the system which can be delimited by means of the LED.

LED

Fault

Fault removal

green 

Power

 LED

does not light up

Supply voltage is missing,

too low or

incorrectly connected.

Check connections and supply voltage:

- 230 V AC (or 120 V) at terminals 

A1 A2

 or

- 24 V AC/DC at terminals 

B1 B2

Tolerance range: ±10%

green 

Power

 LED

flashes cyclically

(pulse output)

Internal fault is indicated

by the number of pulses.

See -> signal displays

red 

CH1

 LED

lights up

The corresponding sensor

is recognized

as being operated.

- Check the connections of the corresponding sensors

  (squeezed or brittle supply lines, etc.)

- Check signal sensor *

red 

CH1

 LED

fast flashing

Sensor circuit interrupted,

sensor not connected,

defectively connected or

defective.

- Check the connections of the corresponding sensors

  (squeezed or brittle supply lines, etc.)

- Check signal sensor *

red 

CH1

 LED

slow flashing

Fault self-retaining

Carry out manual reset

*  If the fault is not found in the wiring, the function of the electronic system can be checked by applying

 

a resistance of 8.2 kΩ to the sensor-input on the switching device. Subsequently, if the electronics work

 

perfectly, the sensor must be checked by means of an ohmmeter. For this purpose, the connection of

 

the sensor to the switching device must be separated and connected by means of an ohmmeter. In the

 

case of a non-operated sensor the resistance must be 8.2 kΩ ± 500 Ω. If the sensor is operated, the

 

resistance must not exceed 500 Ω.

12. Decommissioning and disposal

The products manufactured by ASO are exclusively intended for commercial use (B2B). At the end of use, the

 

products must be disposed of according to all local, regional and national regulations. ASO is also happy to

 

take back the products and disposes of them properly.

Содержание 41-322

Страница 1: ...ELMON rail 41 822 ELMON rail 41 322 Safety relais Operating Manual see last page for validity ELMON rail 41 822 ELMON rail 41 322 Safety Relais English Page 03 14 U S Edition 2017 ASO GmbH ...

Страница 2: ...upplémentaires Componenti ausiliari Bijkomende componenten Funktionsprüfung Functional test Contrôle de fonction Controllo funzionale Functiecontrole Sicherheitssensoren reagieren auf Betätigung Safety sensor response to actuation Le senseur de sécurité réagit à l actionnement Il sensore di sicurezza reagisce all azionamento Veiligheidssensor reageert op activering Sicherheitssensoren reagieren au...

Страница 3: ...ety output 8 7 2 Automatic reset 8 7 3 Fault self retaining manual reset 8 7 4 Signaling output without any delay RLU 8 7 5 Signaling output delayed RL 8 8 Mechanical mounting 9 9 Electrical connection 9 9 1 Supply voltage 9 9 2 Connection of sensor 9 9 3 Connection of multiple sensors per sensor circuit 9 9 4 Connection of control circuits 10 9 5 Connection Reset 10 9 6 Connection of signaling co...

Страница 4: ...ructions must be followed and adhered to unconditionally Electrical work must only be carried out by skilled electricians Safety regulations for electrical engineering and from the professional association must be followed In case work has to be carried out on the switching device it must be switched to a voltage free position and checked for freedom from any voltage and secured against being swit...

Страница 5: ... It is not fail safe and not checked by testing either The switching device has been designed and type approved in accordance with EN ISO 13849 1 Safety related parts of control systems for category 3 Performance Level e For compliance with category 3 the safety output is set up redundantly with two independent switching elements In addition the device has been type approved according to EN 62061 ...

Страница 6: ... specifications Any use for special applications requires prior release by the manufacturer 5 Application example Safety orientated monitoring of a safety contact edge with start release via release pushbutton and separate continuation of the control circuits category 3 compliant application according to EN ISO 13849 1 In order to check the functionality of the load breaking K1 and K2 relays the b...

Страница 7: ...e Application Example 24V M 13 14 K2 23 24 33 34 L1 L2 L3 31 8 2ΚΩ 14 K1 24 34 13 23 33 23 13 X2 X1 B1 X4 X3 S1 32 24 14 B2 Z2 Z1 41 41 42 42 K2 K1 X1 Reset 0V S1 S n 8k2 Ω 24V M 13 14 K2 23 24 33 34 L1 L2 L3 31 8 2ΚΩ 14 K1 24 34 13 23 33 23 13 X2 X1 B1 X4 X3 S1 32 24 14 B2 Z2 Z1 41 41 42 42 K2 K1 X1 Reset 0V ...

Страница 8: ...8 Safety relais 5 4 4 Wire Multiple Application Example 24V M 13 14 K2 23 24 33 34 L1 L2 L3 31 8 2ΚΩ 14 K1 24 34 13 23 33 23 13 X2 X1 B1 X4 X3 S1 32 24 14 B2 Z2 Z1 41 41 42 42 K2 K1 X1 Reset 0V S1 S n ...

Страница 9: ... output indicates the fault Pulse Fault alarm 1 Voltage supply outside the valid value range 2 Fault when testing signal input 3 Output control relay faulty 4 Data transmission between micro controllers faulty 6 3 Connection terminals A1 A2 ELMON rail 41 822 Supply voltage 120 V 50 60 Hz ELMON rail 41 322 Supply voltage 230 V 50 60 Hz B1 B2 Supply voltage 24 V AC DC X1 X2 Connection sensor X3 X4 I...

Страница 10: ...cturer is liable for incorrect settings or missuse 7 3 Fault self retaining manual reset S1 OFF Following removal a fault of in a sensor circuit or after a voltage failure the switching unit will only release the output s again if the Z1 and Z2 contacts 500 ms after the elimination of the disruption are closed by means of a pushbutton This completely prevents any automatic re start A permanent bri...

Страница 11: ...24 V AC DC the voltage must correspond to the requirements for protective low voltages SELV The supply line to the switching device must be protected by means of a 5x20 glass tube fuse 200mA medium time lag Never apply both voltages simultaneously The 120 V 230 V supply voltage must be applied to the A1 and A2 terminals For operation with 24 V the supply voltage must be applied to the B1 and B2 te...

Страница 12: ...ircuit to be monitored to the 13 and 24 terminals If the switching contacts are redundantly continued the factory inserted bridge between the 14 and 23 terminals must be removed In the event of any redundant use of the switching contacts only voltages with the same potential may be connected The use of different voltage potentials does not correspond to any intended use within specifications Depen...

Страница 13: ...or 120 V at terminals A1 A2 or 24 V AC DC at terminals B1 B2 Tolerance range 10 green Power LED flashes cyclically pulse output Internal fault is indicated by the number of pulses See signal displays red CH1 LED lights up The corresponding sensor is recognized as being operated Check the connections of the corresponding sensors squeezed or brittle supply lines etc Check signal sensor red CH1 LED f...

Страница 14: ...fuse glass tube 5x20 Safety relay Max switching current 2 A 24 V AC DC Mechanical service life 106 operations Operating mode RL Switch on delay 0 5 Sek Operating mode RL Switch on duration 3 sec Signal relay Housing Polyamide PA 6 6 Self extinguishing according to UL 94 V2 Dimensions HxWxD 99 x 22 5 x 114 mm Protection type IP20 Protection class II protective insulation Pollution Degree 2 Overvolt...

Страница 15: ...nce with applicable code of practice If this equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired In no event will the manufacturer be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment The examples and diagrams in this manual are included solely for illustrative pur...

Страница 16: ... result of its conception and construction as well as the design we put on the market Machine Directive 2006 42 EC EN ISO 13849 1 2015 EN ISO 13849 2 2013 2 EN 62061 2013 09 EN 60947 5 1 2010 04 EN 61000 6 2 2005 EN 61000 6 3 2007 EC type approval Notified Body 0044 TÜV NORD CERT GmbH Langemarckstraße 20 D 45141 Essen EC type examination no 44 205 13031827 This declaration of conformity does not a...

Страница 17: ...17 Notes ELMON rail 41 822 ELMON rail 41 322 Safety relais ...

Страница 18: ...18 Notes Safety relais ...

Страница 19: ...19 Notes ELMON rail 41 822 ELMON rail 41 322 Safety relais ...

Страница 20: ... be assumed for errors or misprints This operating manual is valid for the following versions from V 1 0 to V 5 1 English Safety relais ASO Safety Solutions Inc 300 Roundhill Drive Unit 6 Rockaway NJ 07866 Phone 1 973 586 9600 Fax 1 973 784 4994 www asosafety com e mail sales us asosafety com ...

Отзывы: