18
UM/SWHM/V3/0115
16
Press DOWN key to go to
the next parameter
Row: ryb dG. (Default)
Phase selection in DG
(
only in 3 phase meter
)
It defines which phase needs to be
work in DG.
Ranges: ryb,r,y,b
17
Press UP key to select the
edited value.
Row: ryb dG.
Selected mode blinks and
select any of the phase
selection as mentioned in
the range using DOWN
key. Press UP key to
accept the selected mode.
18
Press DOWN key to go to
the next parameter
Row : display 285.0 O.V
(over voltage)
285.0 O.V (Default)
Defines the over voltage settings
between Line to neutral.
Range: 80-310 V
19
Press UP key to select the
over voltage value
Row: 285.0 O.V (Over
Voltage)
First digit blinking can be
edited using DOWN key.
(selected mode blinks)
20
Press UP key to accept the
edited value for first digit.
Row : 285.0 O.V
Second digit blinking, can
be edited using DOWN
key. Press UP key to
accept the edited value.
Continue the same
method until fourth digit.
Program Range for Over Voltage :
80V to 310V
If value set is above this limit,
display returns to the maximum O.V
value acceptable
.
21
Press DOWN key to go to
the next parameter
Row: 5.000 d.t (Delay
Time). Follow the
procedure as described in
steps 5 & 6
5.000 (default)
It defines the delay time for relay
tripping
Range: 1-180 sec
22
Press DOWN key
Row : 9600.b (Baud rate)
Communication Speed
(9600-Default / factory
set)
Defines the Baud rate Option:
2400, 4800, 9600, 19.2k.
23
Press DOWN key
Row : EVEn P (Parity)
Even/ Odd/ None
Even(even)/ Odd( odd)/ No( No
parity)
(Internal Communication error
Check)
24
Press DOWN key
Row : 1.000 Id( Device ID)
1.000 (Default)
Defines the ID.
Communication identification
Number. Option :1- 247
25
Press DOWN key
Row: ------ (Password).
User Programmable
password, range 1000 to
9999.
If the password is forgotten the
meter will be reset and calibrated
at factory only.
20
Press DOWN key
Row : rESO E.S (Energy
Selection) rESO (Default)
Option: resolution/counter
(rESO/COUN).Energy value format
i.e., the energy accumulated in the
meter to be displayed in resolution
or counter format