Technical Support Line +44 (0)23 9269 6638 (Option 3) POE-MINIPOD          PAK200793_01A Nov 2016             © 2016 Elmdene International Ltd 

 

C

ONNECTIONS

   

INPUT 

PoE802.3at connection from PoE+ source

 

OUTPUT 

PoE802.3at connection to PD

 

FAULT: 

Relay output for PoE+ fail. Open if loss of PoE+. 

BATT +, - 

Connection to standby battery. Use cables provided (Observe polarity)

 

I

NSTALLATION 

I

NSTRUCTIONS

 

 

 

This  unit  is  only  suitable  for  installation  as  permanently  connected  equipment.    This  PSU  is

 

SUITABLE 

for  external 

installation. This unit must be fed from a PoE802.3at power source. 

 

Mounting 

1)

 

Mount securely in correct orientation (RJ45 glands facing downwards) using the wall brackets provided 

 

Power Up 

2)

 

Attach suitable cable from PoE+ source to INPUT RJ45 connector 

3)

 

Attach suitable cable between PD and OUTPUT RJ45 connector 

4)

 

Connect charged 12V 7Ah VRLA battery using cables provided 

NOTE:

 ensure correct polarity of battery connections: 

+ve

 use 

Red

 lead, 

-ve

 use 

Black

 lead. 

5)

 

Observe RED LED is ON when PoE+ is present 

6)

 

Observe PD indicates power is present 

7)

 

Remove INPUT cable from POE-MINIPOD and observe PD continues to indicate power is present 

8)

 

Reconnect INPUT cable  

 

Signalling 

9)

 

Connect fault output to appropriate inputs of Control and Indicating Equipment (CIE) if required. 

10)

 

Close cover and secure using fastening key provided. 

To PD  
e.g. PoE Camera 

To Switch / PoE+ source 

Fuse 

Battery connection 
+ve / -ve 

Fault 
Output 

OUTPUT (pre-wired) 

INPUT (pre-wired) 