2
Technical Support: +44(0)23 9269 6638 (option 3)
PAK200035_07A Oct 2014 ©2014 ELMDENE INTERNATIONAL LTD
JP1: Cut-off timer for alarm (R-)
Link = no cut-off (default)
No link = sounder cut-off after 15 minutes
VR1: Volume control for entry/exit/keypad low level tone (M-)
Figure 1. Connections and Timer Selection Jumper
With the cut-off timer link NOT fitted, the
INT600(S)
sounder will automatically stop sounding after 15
minutes, irrespective of the status of the sound trigger (R-) input.
SAB
M
ODE
(INT600S
O
NLY
)
SAB mode is enabled if the internal battery is connected, the unit will then self-activate if the tamper is
activated or the supply cut.
C
ONNECTIONS
R-
Negative siren trigger for alarm. Apply 0V to activate sounder
M-
Negative low volume trigger for entry/exit/keypad. Apply 0V to activate.
ST-
Not applicable.
H+
Permanent positive hold-off supply, +12Vdc nominal
H-
Permanent negative hold-off supply
TR
Volt free tamper connection
TS
Volt free tamper connection
BT-
SAB Battery negative
BT+
SAB Battery positive
C
OMMISSIONING
1)
Remove cover.
2)
Offer backplate to desired position on
mounting surface and drill holes to match
chosen fixing centres.
3)
Fix backplate to mounting surface using
appropriate fixings for the mounting surface.
4)
Set the required Cut-off Timer using JP1.
5)
Loop the connection cable three times through the supplied ferrite as shown.
6)
C12V dc and 0V supply from the control panel to H+ and H- respectively.
7)
Connect R- to Ring or Bell output of the control panel.
8)
Connect TS to H- and TR to tamper return of panel for 0V tamper return, or use TS & TR as volt free
contacts without link between TS & H-.
9)
If low output tone facility is used, connect M- to control panel ‘keypad follow’ or a programmable
output.
10)
For SAB facility (INT600S only) connect the battery wires to BT+ and BT-, ensuring correct polarity.
NOTE: The unit will sound until the cover is replaced.
S
OUND
C
UT
-O
FF
T
IMER
V
R
1
ST-
M- R- H+ H- TR TS BT+ BT-
JP1