background image

 

 

Technical Support: +44(0)23 9269 6638 (option 3) 

 

PAK200824_01A   May 2017         ©2017 ELMDENE INTERNATIONAL LTD  

 

Figure 2 – Power, Load and Battery connections 
 

5)

 

Connect the load (output) wiring as shown in Figure 2.   

6)

 

Re-apply mains. Verify that the green Mains LED illuminates and the yellow Fault LED flashes after 
approximately 20s (disconnected battery). 

7)

 

If connected, verify that the EPS Fault monitor shows a 

closed

 contact and the PSU Fault monitor 

shows an 

open

 contact. 

8)

 

Perform a full functional test of system including full alarm condition. 

9)

 

Disconnect the mains supply. 

 

 

 

 

 

 

Figure 3 – Terminal labels

 

 
Standby Battery 

10)

 

Select the Battery type by placing the link (above the Battery fuse) in the appropriate location to 
select (17/18Ah, 38Ah or 65Ah) batteries. This changes the maximum bulk charge current, and 
therefore enables higher load current to be used when smaller batteries are required. Put the link 
on the left hand two pins for 17Ah, the middle pins for 38Ah and the right hand two pins for 65Ah 
batteries.  

 
 
 
 
 

Figure 6 – Standby battery size selection links

 

 
11)

 

Connect the two 12V standby batteries in series using the single cable provided. Connect the 

negative

 of one battery to the 

positive

 of the other. 

DO NOT CONNECT

 the other two battery 

terminals to each other. 

12)

 

Connect the free Positive and Negative terminals of the batteries to the PCB terminals Batt+ and 
Batt - using the cables provided. See Figures 2 & 3. 

13)

 

Connect the battery temperature sensor (two white wires) to the PCB terminals TMP Sens. See 
Figure 3. 

14)

 

If the batteries are housed remotely and the standard battery leads are not long enough, use the 
extended battery lead assembly, part No BAT-LD-T-24-300. Ensure temperature sensor and battery 
connections are made according to figure 3. 

15)

 

Re-apply the mains power and verify that the yellow Fault LED stops flashing after about 20s 
(battery connection detected). Verify that the remote GEN PSU Fault monitor shows a 

closed

 

contact. 

16)

 

Disconnect the mains power. Verify that the green Mains LED extinguishes and the yellow Fault LED 
starts to pulse (indicating that the PSU is running from its standby batteries). 

17)

 

If connected, verify that the EPS Fault monitor shows an 

open

 contact and the PSU Fault monitor 

shows a 

closed

 contact. 

18)

 

Perform a full functional test of system including full alarm condition. Verify that the standby 
batteries can support the system load. Note: ensure batteries have sufficient charge. 

Final 

19)

 

Reconnect the mains. Verify that the green Mains LED illuminates and the yellow Fault LED 
extinguishes. 

 n/c |GEN| EPS|TMP|+  - | +  +   -   - 
        |  FAULT    |Sens|Bat|    O/P 

 L     E     N 
    AC  in 

 BATTERY   | DIAG|  OUTPUT LOAD 
 FUSE          |   LED|          FUSE 

 

Main input 

        Fuse 

17/ 18 Ah 

38 Ah 

65 Ah 

Содержание G2410BMU

Страница 1: ...for extended periods Two sets of volt free solid state relay fault outputs signal i loss of mains and ii battery fault charger fault and loss of output In addition there is an RS232 serial interface that can provide diagnostic and fault reporting information to supervisory systems Up to 10A current to load at 27 6V dc nominal regulated output Charging capability to support 18 38 or 65Ah batteries ...

Страница 2: ...h charging Imax A 220V With charging Imax A 110V 10 0A 10 0A 8 5A 10 0A 8 0A 7 5A 10 0A 7 2A 6 5A Battery Capacity eg PowerSonic model Yuasa model 2 x 17 18Ah 12V PS12170 NP17 12 2 x 38Ah 12V PS12380 NP38 12 2 x 65Ah 12V PS12650 NP65 12 Battery Charging Constant current bulk charging to 80 capacity within 24 hours Float charging to 100 within 48 hours Eco charging and check every 2 hours for 20 mi...

Страница 3: ...uts EPS Fault GEN Fault Condition Possible Cause Action CLOSED CLOSED Normal operation Mains present Battery healthy None OPEN CLOSED Standby Mode Mains lost Battery driving load Investigate loss of mains CLOSED OPEN Fault Present Blown fuses Battery fault Overload Internal fault Investigate fault source using diagnostic LED Rectify fault where possible OPEN OPEN PSU Shutdown Mains lost Standby ba...

Страница 4: ...rn to manufacturer 5 PULSES ON or OFF Battery Temperature Probe Fault Battery temperature monitor disconnected or damaged PSU running in Safe Mode Check temperature sensor connections and condition of sensor Replace if suspect ON CONTINUOUS ON or OFF Internal Fault Software fault detected PSU running in Safe Mode Return to manufacturer INSTALLATION This unit is only suitable for installation as pe...

Страница 5: ...eat dissipation and adequate ventilation to avoid overheating of the unit or associated batteries Figure 1 Fixing points COMMISSIONING Mains Power Up 1 With no external connections made to the PSU connect the mains input wires to the terminal block ensuring that the mains isolator disconnect device is open Fasten wiring in place with cable tie to saddle Note Equipment must be earthed 2 Apply mains...

Страница 6: ...battery terminals to each other 12 Connect the free Positive and Negative terminals of the batteries to the PCB terminals Batt and Batt using the cables provided See Figures 2 3 13 Connect the battery temperature sensor two white wires to the PCB terminals TMP Sens See Figure 3 14 If the batteries are housed remotely and the standard battery leads are not long enough use the extended battery lead ...

Страница 7: ...or use by Service Personnel only There are NO USER SERVICEABLE parts inside There is no regular maintenance required of the PSU other than periodic testing and replacement of the standby battery Reference should be made to the battery manufacturer s documentation to determine typical expected battery life with a view to periodic replacement of the battery DIAGNOSTICS Local Diagnostics Green LED On...

Страница 8: ...efore disposal of the product any batteries must be removed and disposed separately via an appropriate approved battery disposal route in accordance with all national and local regulations Package used batteries safely for onward transport to your supplier collection point or disposal facility Caution Risk of fire or explosion if bare battery wires are allowed to touch See Specification for batter...

Отзывы: