Technical Support: +44(0)23 9269 6638 (option 3) 

  PAK200415_01C May 2016                        ©2016 ELMDENE INTERNATIONAL LTD  

C

ONNECTIONS

 

 

LOAD +, - 

Connection to equipment to be powered (Observe polarity) 

 

BATT1 +, - 

Connection to standby battery 1. Use cables provided (Observe polarity) 

 

BATT2 +, - 

Connection to standby battery 2. Use cables provided (Observe polarity) 

APS FAULT 

Relay output for battery fail. Open if battery fail or open for low output. 

EPS FAULT 

Relay output for mains fail. Open if loss of mains. 

PSU FAULT 

Relay output for General Fault. Open in fault condition 

 

I

NSTALLATION 

&

 

C

OMMISSIONING

 

 

This unit is only suitable for installation as permanently connected equipment and must be used with 

DC appliances only

The PSU is NOT SUITABLE for external installation. The PSU should be installed according  to all relevant safety regulations 
applicable to the application. 

This unit must be fed from a mains power source having a separate (approved) disconnect device and fitted with a fuse or 
other over-current protection device rated at 3A maximum. Ensure that the disconnect device used has appropriate earth 
fault protection to the applicable standard. 

Mounting 

1)

 

Mount securely into host enclosure allowing minimum clearance around chassis plate - see Fig. 1.0. 

Mains Power Up 

2)

 

Attach correctly rated mains cable and fasten using cable ties. 

3)

 

Apply mains power. Check for 13.8v (nominal) on load outputs. Check green Mains LED is on. 

4)

 

Disconnect mains power.  

Load Output 

5)

 

Attach correctly rated load cable(s) and fasten using cable ties and adhesive saddles. 

6)

 

Attach correctly rated fault signalling cable(s) and fasten using cable ties and adhesive saddles. 

7)

 

Attach supplied battery cables to terminal block and battery. NOTE: ensure correct polarity of battery connections: 

+ve

 use 

red

 lead, 

-ve

 use 

black

 lead. 

8)

 

Apply mains power. Check green Mains LED is on. 

9)

 

Check there is no fault indication on the Red LEDs. A single short flash indicates that the corresponding battery is not 
fully charged and is being charged. – This is OK. 

10)

 

Disconnect mains power. Check that the batteries continue to supply voltage and current to the load. NOTE: batteries 
must have sufficient charge.  

11)

 

Reconnect mains. 

 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig 1.0 Mounting the Power Supply 

 
 
 
 

 

Mains input cable rating: 
>3A, 300Vac minimum 
 
Load output cable: 
Current rating to match 
Maximum load. 
 
 

N E L

FUSED

SPUR

3A

MIN

MINIMUM 

CLEARANCE WITH 

WALLS OF HOST 

ENCLOSURE

CHASSIS

ENCLOSURE